combustible materials of explosion groups IIA, IIB, IIC and IIIA, IIIB, IIIC.
The VEGAPULS C 21, C 22, C 23 are suitable for applications requiring EPL Gb instruments.
The VEGAPULS C 21, C 22, C 23 are suitable for applications requiring EPL Da instruments.
The VEGAPULS C 21, C 22, C 23 are suitable for applications requiring EPL Da/Db instruments.
4

Application area

EPL Gb instrument
The VEGAPULS C 21, C 22, C 23 with the mechanical fixing element are installed in hazardous
areas of zone 1 requiring EPL Gb instruments.
EPL Da instrument
The VEGAPULS C 21, C 22, C 23 with the mechanical fixing element are installed in hazardous
areas of zone 20 requiring EPL Da instruments.
EPL Da/Db instrument
The VEGAPULS C 21, C 22, C 23 with mechanical fixing element are installed in hazardous areas
of zone 21 requiring EPL Db instruments. The mechanical fixing element, process connection ele-
ment is installed in the separating wall, which separates areas requiring EPL Db or EPL Da instru-
ments. The sensor measuring system is installed in hazardous areas of zone 20 requiring EPL Da
instruments.
5
Specific conditions of use ("X" identification)
The following overview is listing all special properties of VEGAPULS C 21, C 22, C 23, which make
a labelling with the symbol "X" behind the certificate number necessary.
Electrostatic charging (ESD)
You can find the details in chapter " Electrostatic charging (ESD)" of these safety instructions.
Ambient temperature
You can find the details in chapter " Thermal data" of these safety instructions.
Impact resistance
The VEGAPULS C 21, C 22, C 23 have been subjected to the test according to the standard cor-
responding to a low degree of mechanical hazard (4J).
6
Additional instructions for safe operation
For process pressures outside the standard atmospheric conditions of 80 kPa (0.8 bar) to
110 kPa (1.1 bar) additional requirements can be valid.
Connection conditions
For fixed installation, the connecting cable is suitable for an operating temperature range of
-40 ... +80 °C. The temperature at the connection cable may be +90 °C for max. 10000 operat-
ing hours.
For flexible installation, the connecting cable is suitable for an operating temperature range of
-25 ... +80 °C. The temperature at the connection cable may be +90 °C for max. 10000 operat-
ing hours.
If necessary, a suitable overvoltage arrester can be connected in front of the VEGAPULS C 21,
C 22, C 23