Outdoor Unit Installation; Installation Place - EAS ELECTRIC EVR6 Serie Manual De Instrucciones

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

When installing the outdoor unit in a place that is constantly
exposed to a strong wind such as the upper stairs or rooftop of a
building, apply the windproof measures referring to the following
examples.
Install the unit so that its discharge port faces to the wall of the
building. Keep a distance 3000mm or more between the unit and
the wall surface.
Do not mount the outdoor unit on a wall.
Supposing the wind direction during the operation season of the
discharge port is set at right angle to the wind direction.
Strong
wind
Installation in the following places may result in some troubles.
Do not install the unit in such places below.
A place full of machine oil.
A place full of sulphuric gas.
A place where high-frequency radio waves are likely to be
generated as from audio quipment, welders, and medical
equipment.

3. OUTDOOR UNIT INSTALLATION

3.1 Installation place

Please keep away from the following place, or malfunction of the
machine may be caused:
There is combustible gas leakage.
There is much oil (including engine oil) ingredient.
There is salty air surrounding(near the coast)
There is caustic gas (the sulfide, for example) existing in the
air (near a hotspring)
A place the heat air expelled out from the outdoor unit can
reach your neighbor's window.
A place that the noise interferes your neighbors every day
life.
A place that is too weak to bear the weight of the unit
Uneven place.
Insufficient ventilation place.
Near a private power station or high Frequency equipment.
Install indoor unit, outdoor unit, power cord and connecting
wire at least 1m away from TV set or radio to prevent noise or
picture interference.
3000
Fig.2-1
Strong
wind
Fig.2-2
The insulation of the metal parts of the building and the air
conditioner should comply with the regulation of National Electric
Standard.
Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions
and radios. This is to prevent image interference and
noise in those electrical appliances. (Noise may be
generated depending on the conditions under which the
electric wave is generated, even if 1 meter is kept.)
3.2 Installation space (Unit:mm)
Single unit installation
Air inlet
>300
Air inlet
Parallel connect the two units or above
>300
>3000
Parallel connect the front with rear sides
>3000
>1000
11
CAUTION
1120
668
206
(Wall or obstacle)
Maintain the electric
wire and pipeline
>600
Air outlet
>600
>6000
>4000
Fig.3-1
Fig.3-2
Fig.3-3
>300
Fig.3-4
V.1

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Evro120vEvro140vEvro160vEvro200y6Evro260y6Evro335y6

Tabla de contenido