05-704
Read the complete manual before attempting installation and
activating the system.
1. DESCRIPTION
Modular dimmer for DIN rail mounting. Width 17,5mm (1 module). Phase
control mode ("triac" dimmer). Maximum load 450W/450VA. Suitable
for incandescent lamps, dimmable wound transformers and electronic
transformers specially provided for phase control. These loads can be
combined. Provided with a Powerline filter. Remote control via normal open
contacts. Maximum 30 non-lit push-buttons in parallel.
This product is in accordance with the EN60669-2-1 and EN 55015
standard.
2. OPERATION
Lamps connected via dimmers cannot be activated to the maximum light
intensity. The amount of light will always be smaller when compared with
an identical lamp that is directly connected to the network. In case of a
full charge, the dimmer will dissipate max 5W.
Remote control via NO contacts (not lit). Press briefly to switch on or off.
Press longer to decrease or increase. When pressing long, the direction
is reversed with each interruption (increase -> stop -> decrease -> stop
-> increase -> etc). Once the maximum intensity is reached, the level will
remain the same even if the push-button is pressed longer. The last level
before switching off can be saved in the memory (cfr. §2.1). Up to 30 NO
contacts Niko ref. 170-0000X can be connected in parallel (max distance
100m). The push-buttons are not galvanicly isolated.
The dimmer is equipped with a system that prevents flicker in case of a
sudden decrease of the mains frequency. Frequency dips up to 3Hz are
set off by reducing the light intensity. The dimmer can be set to maximum
with the next operation. After switching on the mains voltage it can take
up to 20s. (40Hz) before the dimmer can be operated, depending on the
mains frequency.
2.1 Memory function
The dimmer can be used with or without memory.
This mode is factory preset. Hold the push-button closed for 10 seconds
to modify this mode. After 10 seconds the light level will switch from the
maximum to 50%. Release the push button immediately when this happens.
The memory mode is now de-activated
Repeat this action to re-activate the memory mode. This mode selection
and the last lighting level are saved in the memory. Settings are not lost
when the power is switched off.
With memory function the dimmer is activated on the minimum light
intensity the first time. Subsequently the dimmer is switched on with the
last set value.
With memory
Short contact = on at memorised level/off
Long contact following off = dimming up
Dimming up: dimmer stops at maximum light intensity
Dimming down: light level stops 2s. at min and starts increasing again
Dimming down: dimmer stops at min, then short contact = lights off
Each new (long) contact inverses the dimming direction.
Without memory
Short contact = on at maximum level/off. The rest of the operation is
analogous to the operation with memory.
Remote control by push-button control:
Short contact <400ms
Long contact >400ms
= on/off
= increase/decrease
22 Derating tabel
Type
Symbol
Maximum load
Resistive
R
450W
Inductive
L
450W
Capacitive
C
not authorised
Power, 50Hz
Vermogen bij 50Hz
470
450
430
410
390
370
0
35
If the dimmers are placed next to each other, the max load is 80%.
2.3 Attention
- The dimmer includes a triac and a coil that can cause vibration or buzzing.
This can be audible depending on load and the light level.
- When mounting the dimmer near to an audio installation it is recom-
mended to provide the connecting wires between the different parts of
the installation with shielded wire.
- Signals sent via the mains can disturb the functioning of the dimmer. A
CAB filter is built in to suppress this effect.
- When used normally, this dimmer will produce a limited amount of heat.
nv Niko sa
You have to provide a heat outlet. Do not cover the dimmer with isolating
material. Keep in mind that the maximum amount of power is limited
when several dimmers are placed on top of or next to each other.
- When several dimmers are built into a distribution board, the temperature
in this board can be higher than the ambient temperature. This can influ-
ence the functioning of the dimmer (limited maximum amount of power
– thermal protection). Provide enough ventilation in the distribution board
so that the board temperature is always lower than the ta value indicated
on the appliance (35°C). Do not place them next to each other when they
are all loaded to the maximum.
- The use of mixed loads (inductive + capacitive electronic transformers,
symbols L and C) is not allowed.
- Mixed use with special electronic transformers provided for phase control
mode (symbols R or L on the transformer) is allowed.
- When using halogen lighting with ferromagnetic transformers, pay atten-
tion to the output of the transformers. Load these transformers with at
least 80% of their normal amount of power. Pay attention to the output
of the used transformer when determining the total load of the dimmer.
The transformer has to be suited for dimming.
- Electronic transformers can be out of balance when the wire length
between the transformers and the lamps is longer than 2 metres.
- Conduct of the appliance after power cut-off: back to previous situation
with memory/off without memory.
- The dimmer is never de-connected electrically from the mains by operating
the control. All parts are therefore always live even if the load (e.g. the
light) is switched "off".
- If necessary, always replace the fuse by the indicated type.
- These dimmers are not suitable for controlling motors unless the specific
safety requirements are guaranteed by external systems.
3. MAINTENANCE OF THE PRODUCT
- Regular controlling of the connections and the ventilation in the cup-
board.
4. TROUBLESHOOTING
The dimmer is supplied with a green LED which indicates the load condi-
tion.
If the LED is not lit:
- the dimmer is turned off
- the mains voltage is not connected
- the fuse has melted
- the load is not connected
- the lamp is defective
- the thermal protection is activated
- combination of the above-mentioned causes
Checking the fuse:
- Interrupt power supply bipolarly
- Open fuse holder by pressing simultaneously and turning 90° to the
left
- Measure the fuse resistance
- Only replace fuse by original type F3,15AH Niko-ref. 04-226-20
The dimmer is provided with thermal protection. If the temperature rises
too high, the dimmer is switched off. The dimmer automatically switches
back on as soon as the temperature has dropped sufficiently.
In this case you should:
- Check whether the load is not too high, considering the power factor or
efficiency of the ferromagnetic transformers.
- Check the temperature in the distribution board (max 35°C). If this is too
high, you need to provide extra ventilation. Provide an outlet on the top
of the board. Install a ventilator if necessary.
- If several modules are placed next to each other: provide an interspace
of at least 1 module via adjusted blind panels.
5. TECHNICAL DATA
- Mains supply: 230V~ ±10%, frequency 40 to 60Hz
- Dimensions: H 92,4 x D 66 x W 17,5 mm
- Mounting: DIN-rail
- Weight: ±94g
- Ambient temperaturer: t a = 35°C
- For use in an environment with a non-condensing atmospheric humid-
ity
- Consumption: 1,7W
- Maximum temperature of the cover (t c ): 90°C
- Maximum wire diameter per terminal:
- Power supply and load: 2 x 1,5mm
- Push-button input: 2 x 1,5mm
- Minimum load: 40W / 50VA
- Maximum load: cfr. load table
- Voltage drop over dimmer: max. -5%
t a (°C)
50
- Protection:
- thermal protection against overload via automatic reset
- short-circuit protection via built-in ceramic safety fuse, no built-in standby
safety fuse. Fuse is replaceable by original type F3,15AH (04-226-20).
- Push-buttons for controlling: 230V, 5mA (no galvanic isolation)
Industriepark West 40, BE-9100 Sint-Niklaas, Belgium — tel. +32 3 778 90 00 — fax +32 3 777 71 20 — e-mail:
[email protected] — www.niko.be
6. LEGAL WARNINGS
- The installation has to be carried out by a qualified person and in compli-
ance with the statutory regulations.
- This user manual has to be handed over to the user. It has to be included
in the electrical installation file and has to be passed on to any new own-
ers. Additional copies are available on the Niko website or via the support
service.
- During installation, the following has to be taken into account (not limited
to list below):
- The statutory laws, standards and regulations;
- The state of the art technique at the moment of installation;
- This user manual, which must be read within the scope of each specific
- The rules of proper workmanship
- In case of questions, you can consult Niko's support service or contact
In case of a defect, you can return your product to a registered Niko
wholesaler, together with a clear description of your complaint (Conditions
of use, stated defect...).
7. GUARANTEE PROVISIONS
- Period of guarantee: 2 years from date of delivery. The delivery date is
the invoice date of purchase of the product by the consumer. If there is
no invoice, the date of production applies.
- The consumer is obliged to inform Niko in writing about the defect, within
two months after stating the defect.
- In case of a failure to conform, the consumer has the right to a repair or
replacement (decided by Niko) free of charge.
- Niko cannot be held liable for a defect or damage as a result of an incorrect
installation, improper or careless use or wrong usage or transformation
of the goods.
- The compulsory regulations of the national legislation concerning the
sales of consumer goods and the protection of the consumers in the
countries where Niko sells, directly or via sister or daughter companies,
chain stores, distributors, agents or permanent sales representatives,
take priority over the rules and regulations mentioned above.
8. WIRING DIAGRAM
or 1 x 2,5mm
2
2
2
R,L
installation, only states general regulations;
a registered control organisation.
Support Belgium:
Support UK:
+32 3 778 90 80
+44 1525877707
website : http://www.niko.be
http://www.nikouk.com
L
230V~
N
0
F3,15AH250V
R,L
170-0000X
40...450W
50...450VA
230V~50Hz (ta=35 ∞ C)
05-704
1 4
CEBE C
L N
L
230V~
N
0
F3,15AH250V
R,L
170-0000X
40...450W
50...450VA
230V~50Hz (ta=35 ∞ C)
05-704
1 4
CEBE C
L N
PM005-70400R08163