MANUALE D'INSTALLAZIONE E USO
MANUAL
PROPORTIONAL
Codice 1075262
MANUAL OPERATION MODE:
CONSTANT AND INDEPENDENT DOSAGE FROM PH VALUE
Flowrate % = Flowrate % of maximum dosage
The dosage is achieved with pause times and work times on a time
base of 300sec.
Example: 80% the pump doses for 240 seconds (= 0.8 x 300) and
stops for the next 60 seconds. It Repeats this operation indefinitely
PROPORTIONAL OPERATION MODE:
DOSAGE PROPORTIONAL TO THE DISTANCE
OF THE pH MEASURE FROM THE DESIRED
SETPOINT.
Setpoint = measured value that you wish to have
in the system
Proportionality = range of the measured values
in which DUAL adjusts the flowrate of dosage
Regulation Acid (pH -) = dosage for measured
values greater than Setpoint
Regulation Alkaline (pH+) = dosage for
measured values lower than the Setpoint
Flowrate % = maximum dosing flowrate
Delay On = delay time in seconds that Dual waits
to start dosing
pag. 23 a 56
Ver.01 – 19/06/20