MANUALE D'INSTALLAZIONE E USO
CONNECTIONS
PASSWORD = 0 (PASSWORD not programmed)
pH Stability = NO (deactivated)
Start Delay: 6 minutes
pH:
OPERATION TYPE: Proportional
SETPOINT: 7.3 pH
PROPORTIONALITY:1pH
REGULATION DIRECTION: Acid (pH - )
FLOW RATE: 50%
DELAY ON: 3 seconds (0-999sec)
ALARM TIME : 0unit (disabled)
DEFAULT SETTINGS RESTORE
MENU TREE
Push and quickly release CAL button during the functioning to enter into the programming menu. Push + or - button to
navigate through the menu. Push the CAL button to enter the submenus.
LANGUAGE SELECTION
Codice 1075262
A - Power cable, 230 V- 50Hz (upon request : 115 ~ )
B - ON_OFF switch. OPTIONAL
C - BNC connector for pH probe.
D - BNC connector for Amperometric CL probe.
E - Potentiostatic CL probe connector. Connexions on pag 47
F - BNC connector for temperature probe OPTIONAL
G - Level probe connector (3 and 4 contacts) for CL pump.
OPTIONAL
H - Flow sensor connector (3 and 4 contacts). OPTIONAL
I - Alarm output connector (3 and 4 contacts).NORMALLY
OPEN OPTIONAL
L - Level probe connector (3 and 4 contacts) for pH pump.
OPTIONAL
DEFAULT SETTINGS
CL:
OPERATION TYPE: Proportional
SETPOINT: 1.20ppM
PROPORTIONALITY:1ppM
REGULATION DIRECTION: Chlorination
FLOW RATE: 50%
DELAY ON: 3 seconds (0-999sec)
ALARM TIME : 0unit (disabled)
Push and quickly release CAL button to enter programming and then
pressing + and – buttons select "Factory Settings Restore"
Push CAL to confirm the choice. The pump goes back to measure
restoring in memory the default settings and calibrations parameters.
pag. 19 a 56
Ver.01 – 19/06/20