CPV..-GE-ASI-4E4A-...
2
Connecting and display elements
1
2
AS-Interface bus connection
3
LED status display for inputs (green)
4
Sensor connections (PNP)
5
Earth connection
6
Type plate (ID and IO codes)
Inscription field for AS-Interface address
*) Only with type CPV..-GE-ASI-4E4A-Z: Valves can be switched off during
EMERGENCY STOP, no voltage supply to valves via AS-Interface bus
PWR LED
Fault LED
(green)
(red)
on
out
out
out
flashes
on
on
flashes
on
on
16
1
2
0
9
8
Meaning
AS-Interface voltage applied, no fault
No AS-Interface voltage on bus
AS-Interface address not set (zero)
Short circuit/overload at the inputs
Failure of bus communication
(watchdog expired)
3
4
5
6
7
7
LED status display for
8
valves (yellow)
Load voltage connection
9
for valves *)
0
PWR LED (Power, green)
Fault LED (red)
9910b