Location
Locate the instrument in an area that is free from dust, moisture
and corrosive gases.
Cleaning
The case can be wiped with a damp cloth. De-energize the unit
before cleaning.
Connections
Strip wires to 7 mm from the ends. Use a suitable ferrule for
multistranded wires (do not solder).
Use 12-28 AWG Cu Wire rated for temperatures above 70 °C Only,
tighten to 4.5 lb-In.
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
Connections
Terminal
Signal
5
Loop –
6
Loop +
1
Signal +
2
Signal –
6
Output (4-20 mA)
Thermocouple