Connections
Connect the output circuit as shown on page one with the
multimeter in place of the receiving device.
Connect the 931U-C9A2C-OP up to a PC running the setup/
Calibration software (as if you were going to change the setup).
Input Calibration points
Range
Volts/Thermocouple
mA
RTD/Resistance
Individual calibration
Fine adjust
All
14
Values
Notes
10 mV, 20 mV,
If the internal switches are set to 10 V, you must
50 mV, 80 mV,
supply a signal ten times the displayed value, e.g. 10
200 mV, 1 V
V for the 1V point.
20 mA
100 Ω, 200 Ω,
Use four wire mode
500 Ω, 800 Ω,
2 kΩ, 10 kΩ
As selected
Allows you to recalibrate any of the points above
Current input
Fine tune the adjustment for the range you have
selected.
All ranges
Complete calibration of all points. Internal switches
must be in the 1V position.