Allen-Bradley 931U-C9A2C-OP Instrucciones De Operación página 15

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

Input calibration
1. Save the current calibration to disk (select 'Save Calibration
data' from the 'Device' menu).
2. Select 'Calibrate Input' from the 'Device' menu.
3. Enter the calibration password (Default is 101).
4. Choose the calibration required (see Input calibration points
table for guidance).
5. Supply the signals requested by the software and follow the
instructions on screen. Press the 'Done' button when finished.
Output Calibration
1. Measure the output current.
2. Select 'Calibrate output' from the 'Device' menu.
3. Enter the calibration password.
4. The 4 mA adjustment window will open. Adjust the output to
4.00 mA using the buttons shown.
Note: you can use PgUp and PgDn controls on the keyboard for
fine adjustment and <CNTRL> + PgUp and <CNTRL> + PgDn
for coarse adjustment.
5. Press Next when the output has settled at 4.00 mA.
6. Repeat the procedure for the 20.00 mA adjustment.
15
Tabla de contenido
loading

Productos relacionados para Allen-Bradley 931U-C9A2C-OP

Tabla de contenido