Fm Installation Drawing - PR electronics 9203 Manual Del Usuario

Ocultar thumbs Ver también para 9203:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

fm Installation Drawing

LERBAKKEN 10, 8410 RØNDE DENMARK
For safe installation of 9203B the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
For Installation in Zone 2 / Division 2 the following must be observed.
The 4501 programming module is to be used solely with PRelectronics modules. It is
important that the module is undamaged and has not been altered or modified in any way.
Only 4501 modules free of dust and moisture shall be installed.
c-FM-us Certificate
Hazardous area
Class I/II/III, Division 1, Group A,B,C,D,E,F,G
or Class I, Zone 0/1 Group IIC, [AEx ia] IIC or
or Class I, Zone 0/1 Group IIC, [Ex ia] IIC
Simple Apparatus or
Intrinsically safe apparatus
with entity parameters:
Vmax (Ui) ≥ Vt (Uo)
Imax (Ii) ≥ It (Io)
Pi ≥ Pt(Po)
Ca(Co) ≥ C
+ Ci
cable
La(Lo) ≥ L
+ Li
cable
Revision date:
2011-11-20
26
FM Installation drawing
Version Revision
V5 R0
9203 - Product Version 9203-002
3035277
Non Hazardous Area or
Class I, Division 2, Group A,B,C,D T4
or Class I, Zone 2 Group IIC T4
-20 ≤ Ta ≤ 60ºC
4501
44
43
42
41
54
53
52
51
9203
91 92 93 94 95
Power
Rail
Supply / Input
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
m
Prepared by:
PB
9203QF01
34
33
32
31
14
13
12
11
: 253V, max. 400Hz
Page:
1/2

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

9203a 9203b

Tabla de contenido