Technical parameters

Inputs
Temperature measuring:
Scope and accuracy of
temp. measuring:
Number of control buttons:
RFID readers
Supported frequencies:
Card Type:
MIFARE Ultralight, DESFire 2K(EV1), DESFire 4K(EV1)
Outputs
Indication:
Output:
Acustic output:
Switching voltage:
Switching output:
Peak current:
Insulation voltage between
relay outputs and internal
circuits:
Minimal switched current:
Switching frequency without
load:
Switching frequency with
rated load:
Mechanical life:
Electrical life AC1:
Communication
Installation BUS:
Power supply
Supply voltage / tolerance:
Dissipated power:
Rated current:
Connection
Data:
Network:
Operating conditions
Relative humidity:
Operating temperature:
Storing temperature:
Protection degree:
Overvoltage category:
Pollution degree:
Operation position:
Installation:
Dimensions and weight
Dimensions:
Weight:
TECHNICAL SUPPORT | E-mail: [email protected] | Mobil: +420 778 427 366 | Tel.: +420 573 514 276, +420 573 514 211 | Fax: +420 573 514 227 | http://www.inels.com
Made in Czech Republic
GMR3-61
YES, built-in temperature sensor
0 .. +55 °C;
0.3 °C from the range
6
13.56 MHz
3 pairs of LED (red, green)
1x changeover 8A / AgSnO
2
piezo-changer
230V AC / 30V DC
2000 VA/AC1; 240 W/DC
20 A / < 3 s
3.75 kV,
SELV according to EN 60950
10 mA / 10 V
300 min
-1
15 min
-1
7
1x 10
1x 10
5
BUS
27 V DC, -20 / +10 %
max. 2 W
50 mA (at 27V DC), from BUS
terminals, 0.5 - 1 mm
2
2
2
max. 2.5 mm
/ 1.5 mm
with sleeve
max. 80 %
-20 .. +55 °C
-30 .. +70 °C
IP20
II.
2
any
into installation box
94 x 94 x 36 mm
155 g
ELKO EP, s.r.o. | Palackého 493 | 769 01 Holešov, Všetuly | Czech republic | e-mail: [email protected]
Warning
Before the device is installed and operated, read this instruction manual carefully and with full
understanding and Installation Guide System iNELS3. The instruction manual is designated for
mounting the device and for the user of such device. It has to be attached to electro-installation
documentation. The instruction manual can be also found on a web site www.inels.com. Attention,
danger of injury by electrical current! Mounting and connection can be done only by a professional
with an adequate electrical qualifi cation, and all has to be done while observing valid regulations.
Do not touch parts of the device that are energized. Danger of life-threat! While mounting, servicing,
executing any changes, and repairing it is essential to observe safety regulations, norms, directives
and special regulations for working with electrical equipment. Before you start working with the
device, it is essential to have all wires, connected parts, and terminals de-energized. This instruction
manual contains only general directions which need to be applied in a particular installation. In the
course of inspections and maintenance, always check (while de-energized) if terminals are tightened.