Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 15
GMR3-61
Glass wall card reader
EN
Characteristics
• Wall RFID card reader GMR3-61 is designed for reading of contactless media (chip cards, key fobs,
tags, etc.), which are used for controlling access to buildings or parts of buildings.
• With the glass controller GMR3-61 users will appreciate the elegant design and the easy of con-
trol using six touch buttons, which can be assigned diff erent control functions lighting, shading,
scenes, heating, etc.
• GMR3-61 a design element of the (control) system iNELS and is available in black (GMR3-61/B) and
white (GMR3-61/W) variants.
• GMR3-61 reader can be used to control the security system (locking / unlocking) access system
(opening doors, gates, etc.) or appliances (based on assigned rights).
• GMR3-61 supports RFID media with the carrier frequency of 13.56 MHz. Supported card types
MIFARE Ultralight, DESFire 2K (EV1), DESFire 4K (EV1).
• The GMR3-61 is also equipped with 8A relay output with changeover contact AgSnO
be switched directly by reader (or by any controller in the system).
• Between each pair of touch keys is a pair of indicator LEDs (green, red) to indicate the status of the
controlled appliance, or the state of any sensor or actuator in the system.
• Located on each touch button is a blue LED indicator, signalling the touch of a button. Touch-
ing may also be signalled by a vibrating pulse or audible tone - optionally in the software iDM3.
• All variants of GMR3-61 are available in sizes of luxury controllers LOGUS
• GMR3-61 reader is equipped with a sensor of ambient light intensity. Based on information from
the sensor can switch the orientation of blue LEDs on the touch-pad GSB3 or perform various
actions with the software iDM3, eg. To control the lighting circuits in the corridor and others.
• GMR3-61 cannot be installed into multiple frames they are designed for mounting into installa-
tion boxes.
• Package includes:
- 2x 031.01 screws 3x 20 mm flat head frame.
General instrucions
CONNECTION TO THE SYSTEM, INSTALLATION BUS
iNELS3 peripheral units are connected to the system through the BUS installation. Installation
BUS conductors are connected to the terminal units to BUS+ and BUS- terminals, wires cannot be
interchanged. For installation of BUS it is necessary to use a cable with a twisted pair of wires with
a diameter of at least 0.8 mm, the recommended cable is iNELS BUS Cable, whose features best
meet the requirements of the BUS installation. Bearing in mind that in terms of all the properties
is it is possible in most cases also use the cable JYSTY 1x2x0.8 or JYSTY 2x2x0.8, however it
is not recommended as the best option. In the case of a cable with two pairs of twisted wires
it is not possible to use the second pair of the other for modulated signal due to the speed of
communications; it is not possible within one cable to use one pair for one segment BUS and the
second pair for the second segment BUS. For installation of BUS it is vital to ensure that it is kept
at a distance from the power lines of at least 30 cm and must be installed in accordance with its
mechanical properties. To increase mechanical resistance of cables we recommend installation
into a conduit of suitable diameter. BUS topology installation is free except for the ring, wherein
each end of the bus must terminate at the terminals BUS + and BUS- peripheral unit. While
maintaining all the above requirements, the maximum length of one segment of the installation
BUS can reach up to 500 m. Due to the data communication and supply of units in one pair of wires,
it is necessary to keep in mind the diameter of wires with regards to voltage loss on the lead and
the maximum current drawn. The maximum length of the BUS applies provided that they comply
with the tolerance of the supply voltage.
CAPACITY AND CENTRAL UNIT
It is possible to connect to the central unit CU3-01M or CU3-02M two independent BUSes by means
of terminals BUS1+, BUS1- and BUS2+, BUS2-. It is possible to connect to each BUS up to 32 units,
so it is possible to connect directly to the central unit a total of 64 units. It is necessary to comply
with the requirement of a maximum load of one BUS line - maximum up to 1000 mA current. When
connecting units which draw greater than 1A, BPS3-01M with 3A sampling can be used. It is the
sum of the rated currents of the units connected to the BUS line, other units can be connected
using the units MI3-02M, which generate further BUSes. These are connected to the CU3 unit via
the system BUS EBM and you can connect a total of 8 units via EBM BUS to the central unit MI3-02M.
SUPPLYING THE SYSTEM
For supplying power to system units, it is recommended to use the power source of ELKO EP titled
PS3-100/iNELS. We recommend backing up the system with backup batteries connected to the
source of PS3-100/iNELS (see sample diagram of connecting the control system).

GENERAL INFORMATION

To operate the unit, it is necessary that the unit is connected to a central unit CU3 series, connected
to the central unit of the system CU3, or to a system that already contains this unit as its expansion
to include further system.
All unit parameters are set through the central unit CU3-01M in the software iDM3.
There is LED diode on the PCB for indication of supply voltage and communication with the
central unit series CU3. In case that the RUN diode fl ashes at regular intervals, so there is standard
communication between the unit and BUS. If the RUN diode lights permanently, so the unit is
supplied from BUS, but there is no communication between BUS and unit. In case that RUN diode
is OFF, so there is no supply voltage on the terminals BUS+ and BUS-.
Connection
, which can
2
90
(94 x 94 mm).
8-14 V AC/DC
+
BUS
BUS
-
02-62/2017 Rev.1