6. Operation with 43LEC000 module
6.1 Initial power-up
Attention: By default the menus are in English. If you want to choose another language, see item
6.2.3 Language setting.
With the initial power-up of the 43LEC000 Logger the display shows:
43LEC000 Logger enters in normal operation mode:
6.2 Menus
In normal operation mode, press the ENTER button (
ARROW (
) and DOWN ARROW (
There are 3 menus in 43LEC000 Logger setting structure:
1. EVENT HISTORY – viewing the memory LOG events is the system
2. SET DATE/TIME – setting the date and real time clock
3. LANGUAGE – setting a language
6.2.1 – Event viewing (EVENT HISTORY)
In normal operation mode, press the ENTER button (
Press the ENTER button (
last event in the module LOG memory with number, date and time of happening. With pressing the
DOWN ARROW button (
43LEC000 Logger. Use the UP ARROW button (
one.
Press the CANCEL button (
Table of events:
Event
Panel Reset
The RESET button of the control panel has been pressed.
Snd Fault
Fault in the sounder circuit.
Snd Flt Rst
The fault of the sounder circuit is restored.
Snd Enabld
The sounders are enabled.
Snd Disbld
The sounders are disabled.
Fire Zn XХ
Fire in the zone, where ХХ is the zone number.
Test Zn XХ
Test in the zone, where ХХ is the zone number.
Fault Zn XХ
Fault in the zone, where ХХ is the zone number.
Restore Zn ХХ
The zone fault is restored, where ХХ is the zone number.
Disabld Zn XX
Disabled zone, where ХХ is the zone number.
Enabled Zn XX
Enabled zone, where ХХ is the zone number.
Power On
Initial power-up of the 43LEC000 Logger module.
where Х.Х is the software revision of the module.
on the upper row is shown the last event in the system: Power On, and on
the lower - the current set date and time in format DDММ 'YY HH:ММ:SS.
Note: The last event in the system usually is Panel Reset if there is a
connected fire panel to the 43LEC000 Logger module.
) to select a menu.
) to enter the submenu for viewing the LOG events. The display shows the
) the user can review all the events up to the first one at initial power-up
) to exit the menu. The module returns to normal operation mode.
Description
) to enter the menu mode. Use the buttons UP
) to enter the menus mode. The display shows:
) to review the events again from the first to the last