Controller Instructions
Light
Auxiliary output light
active
Service
HACCP
HACCP function
Continuous
Enabled
Cycle
Setting the set point (desired temperature value)
To display or set the set point, proceed as follow:
1. Press the "Set" button for more than 1 second to display the set point.
2. Increase or decrease the value of the set point, using the "
desired value.
3. Press the "Set" button again to confirm the new value.
Alarms with manual reset
The alarms with manual reset can be reset by pressing the "
Manual defrost
As well as the automatic defrost function, a manual defrost can be enabled, if the temperature conditions allow,
by pressing the "
" button for more than 5 sec.
Continuous cycle
Pressing the buttons "
function. During operation in continuous cycle, the compressor continues to operate for the time "cc" and
it stops when it reaches the "cc" time out or the minimum temperature has been reached(AL = minimum
temperature alarm threshold). Continuous cycle setting: "cc" parameter (continuous cycle duration): "cc"=0
never active; "c6" parameter (by passing the alarm after the continuous cycle):"cc" = 0 never active; it avoid or
delays the low temperature alarm after the continuous cycle.
Accessing the configuration parameter (type C)
1. Pressing the "
" and "Set" buttons at the same time for more than 5 sec, the display will show
"00"(password prompt).
2. Use the "
" or "
3. Confirm by pressing "Set".
4. The display will show the first modifiable "C" parameter.
Auxiliary output light
not active
No malfunction
HACCP function
enabled
Not enabled
" and "
" simultaneously for more than 5 seconds enables the continuous cycle
" buttons to display the number "22" (parameter access password).
Anti-sweat heater function
active
Malfunction (eg. EEPROM
error or probe fault)
HACCP alarm (HA and/or
HF) not enabled
Request
" and "
" respectively, until reaching the
" and "
" for more than 5 sec.
20