4. Control panel
HELIOS PROX control unit is equipped with a control panel, with which it is possible to monitor its state of working. The control panel is composed
by three lighting warning lights (led):
•
green warning light that indicates the intensity of the light
•
yellow warning light that indicates the functioning on setting "positioning" and "sensors exclusion"
•
red warning light that indicates the functioning on learning setting and the alarm condition.
By these luminous indicators, it is possible to verify the correct functioning of the control unit and identify the possible malfunctioning.
When voltage is given to the control unit, all the three indicators led will rest lighted up for one second, then they will execute 2 blinking if the
external (or extractible) memory is in use, 3 blinking if it is the internal one. After few seconds, if the sensor of the luminous intensity is present, the
green led will start to blink in a different way according to the intensity of the light registered. With this led it is quite possible to execute the
regulation of the luminous intensity for the automatic opening of the sunshade. In the case in which a condition of alarm is present (wind or rain),
the red led will start to blink for the complete period of alarm (about 7 min.) The functioning of the control unit in learning mode has been
associated also to the red led.
The yellow led indicates the functioning of the device on positioning mode and sensor exclusion according to the way in which it blinks.
5. Devices testing
Once stopped all the connections it is possible to execute a rapid test of the devices applied to the control unit. If the green led blinks rapidly
(about 2 times for second) or if it turns off, disconnect the light sensor (terminal 7) to avoid the dominance of the same one on the manual
controls. From the condition of closed sunshade:
1.
Give tension to the control unit
2.
Press and release the OPEN key (from remote control or from mechanical key)
3.
The sunshade will start to open itself and after ten seconds press the CLOSE key (or the STOP key for CLARUS series) in order to stop
the movement of the sunshade. If the sunshade does not open, invert the cables of the motor.
5.1 Testing of the rain sensor
1.
Put a damp cloth on the surface of the sensor
2.
After few seconds the sunshade will start to close and the red led will
blink signalling the condition of alarm.
3.
Remove the cloth from the sensor
4.
After about ten seconds it will be possible to get out from the alarm
pressing and releasing the learning key present on the card.
5.2 Testing of the wind sensor
1.
Give tension to the control unit
2.
Set the trimmer (see page 2) about at minimum
3.
Make the anemometer turn vigorously
4.
After few seconds the red led will blink signalling the condition of alarm
5.
It is possible to go out from the alarm pressing and releasing the learning
key as soon as the sunshade closes itself again
5.3 Testing of the light sensor
If it would have been necessary to disconnect the light sensor for precedent
tests, reconnect the terminal of the device respecting the scheme on page 2.
Observe with attention the behaviour of the green led present on the control unit
exposing or obscuring the light sensor.
ATTENTION: the functioning or not of the light sensor is based exclusively
on the green led and not on the movement of the sunshade because the
movement happens after a few seconds from the activation of the sensor.
1.
Light up the light sensor
2.
The green led starts to blink rapidly (pay attention that the intensity of the
light must overtakes the value threshold).
3.
Cover the light sensor
4.
The green led stops blinking
6-1621095
rev.9
19-07-2012
WIN EX / WIN DUO
LIGHT SENSOR
LUX
ITA
ENG
Connections rain sensor
RAIN: - Connect the terminal board 3 of the rain sensor to the terminal
board 1 of the control unit HELIOS PROX
- Connect the terminal board 4 of the rain sensor to the terminal 10
of the control unit HELIOS PROX
- Connect to the terminal boards 1 and 2 of the rain sensor a
voltage of 12-24 Vac/dc to supply the heater (not indispensable)
Connections wind/light sensor
WIND DUO : - WHITE AND BLUE cable on input nr.1 terminal board HELIOS
PROX
- GREEN cable on input nr.4 terminal board HELIOS PROX
- YELLOW CABLE on input nr. 7 terminal board HELIOS PROX