Eikon
Arké
Idea
20521
19521
16961
Two rocker push buttons, to complete with 1 or 2-module buttons - 2 modules.
Device to be used as a double or single push button, depending on the button; it
can be pressed both at the top and at the bottom.
CHARACTERISTICS.
• Rated supply voltage: BUS 29 V
• Input: 10 mA
• Button: double or single
• Terminals: TP BUS
• Possible functions:
- ON/OFF switch
- dimmer control
- roller shutter control
- activation of 2 scenarios.
CONFIGURATION.
FOR THE OPERATIONS OF INSTALLATION AND CONFIGURATION, SEE
THE By-me SYSTEM INSTRUCTIONS MANUAL ATTACHED TO THE
CONTROL UNIT.
Configuration must be done with the device without the button to be able to
press the central configuration button.
• Functional blocks: 2, each functional block can belong to at most 4 groups.
• Selecting the functional block (configuration): during group creation, when the
control unit requires pressing the device button:
- press the central configuration button;
- within 3 s, press one of the two right-hand buttons to select the right functional
block or one of the two left-hand buttons to select the left functional block;
- the red LED will come on and the control unit will configure the functional block;
at the end of the operation the red LED will go out.
PARAMETERS.
• For each functional block it is possible to set the operating mode:
- ON/OFF button;
- dimmer control button;
- roller shutter control button;
- scenario control.
• Operation as a dimmer control button:
- pressing the key at the top for less than 0.5 s lights up the load with the dim-
ming at the saved point;
- pressing the key at the top for more than 0.5 s increases brightness until it is
released;
- pressing the key at the bottom for more than 0.5 s decreases brightness until it
is released;
- pressing the key at the bottom for less than 0.5 s switches off the load.
• Operation as a roller shutter control button:
- pressing the key at the top for more than 0.5 s opens the shutter completely; it
stops when fully open or when briefly pressing the key (either at the top or bot-
tom);
- pressing the key at the bottom for more than 0.5 s closes the shutter com-
pletely; it stops when fully closed or when briefly pressing the key (either at the
top or bottom);
- use only roller shutters with a built-in limit switch.
• LED parameters:
- LED off;
- LED with normal operation (on if the associated actuator is ON);
- LED with reverse operation;
- LED always on for location in the dark;
- central LED with normal operation (on if the associated actuator is ON);
- central LED with reverse operation;
- central LED always on for location in the dark.
49400470A0 03 1705
Plana
14521
FRONT VIEW.
A
Eikon
Arké
B
A
Idea
Plana
B
Caption:
A: configuration button
B: led
If the functional block belongs to more than one group, the "LED with normal
operation" and "LED with reverse operation" parameters are not available. In
these cases the control is confirmed by a LED status change for 3 s.
If a double key is used, it is necessary to set the central LED behaviour to
make the status visible. In this case, configure the left-hand button only.
• Default parameters: the buttons are set as ON/OFF push-buttons and
LED in normal operation.
INSTALLATION RULES.
Installation should be carried out observing current installation regulations for electri-
cal systems in the country where the products are installed. For further instructions,
please see the manual attached to the control panel.
CONFORMITY.
EMC directive
Standard EN 50428.
BACK VIEW.
A
B
A
terminals
TP bus
B
Viale Vicenza, 14
36063 Marostica VI - Italy
www.vimar.com