Códigos de alarma / Alarm code
Numero
Fallo /
Descripción Pantalla
Failure
Screen Description
num
0
ALARMAS ACTIVAS
1
FALLO BATERIA DESCARGADA
2
ALARMA BATERIA AL 20%
3
- - - - - - - - - - - - - - - - -
FAILURE PROTECTION SWICHT
4
MOTOR 1
FAILURE PROTECTION SWICHT
5
MOTOR 2
FAILURE PROTECTION SWICHT
6
MOTOR 3
FAILURE PROTECTION SWICHT
7
MOTOR 4
FAILURE PROTECTION SWICHT
8
MOTOR 5
FAILURE PROTECTION SWICHT
9
MOTOR 6
10
INVERTER CONTROL FAILURE
11
COMUNICATION FAILURE
12
PROBE FAILURE
13
ETHERNET FAILURE MASTER
14
INVERTER LOCAL MODE
(**) If all the motor protection switches go off, the system can not works
Actuación a realizar / Action to carry out
Contact with the manufacturer to replace the
internal batery.
Shows that the internal batery load are 20%
- - - - - - - - - - - - - -
The motor 1 protection swicht has been activa-
ted, check the motor and its consumption
The motor 2 protection swicht has been activa-
ted, check the motor and its consumption
The motor 3 protection swicht has been activa-
ted, check the motor and its consumption
The motor 4 protection swicht has been activa-
ted, check the motor and its consumption
The motor 5 protection swicht has been activa-
ted, check the motor and its consumption
The motor 6 protection swicht has been activa-
ted, check the motor and its consumption
There is a problem in the invertir control, see
inverter manual service.
There is a comunication problem between PLC
and the inverter.
Check the correct wiring of the sensor or if the
same is damaged. It does not indicate any value,
value 9999 appears in the main panel. Without
this probe the system may not function.
Indicates that communication with the master of
communications have failed and that the equip-
ment can not be controlled remotely, it is for this
reason that the device is for if in remote mode..
The inverter control are in LOCAL mode, check
teh inverter panel to active the REMOTE mode.
12