PART A: MOUNTING OF THE TOOLS
IMPORTANT!
Only use the original aquatherm welding devices and aquatherm
welding tools, except devices and tools which are especially
approved by aquatherm.
2. Assemble and tighten the cold welding tools manually.
3. Before fusing the distribution block, in which two connections are
fused simultaneously, the welding tools have to be placed into the
respective holes as described in the adjoing table A and drawing B.
4. All welding tools must be free from impurities. Check if they are
clean before assembling. If necessary clean the welding tools with
a non fibrous, coarse tissue and with methylated spirit.
Place the welding tools on the welding device so that there is full
surface contact between the welding tool and the heating plate.
Welding tools over Ø 40 mm must always be fitted to the rear
position of the heating plate.
Electric supply:
The power supply must coincide with the data on the type plate of
the welding device and must be protected according to the local
regulations. To avoide high power loss, the conductor cross-section
of the used extension cables must be selected according to the
power input of the welding devices.
6. Plug in the welding device. The green operating lamp glows
constantly, as soon as the device is conntected with the power
supply system.The temperature pilot lamp glows constantly while
the heat-up phase and blinks, when the welding temperature is
achieved.
Depending on the ambient temperature it takes 10 - 30 minutes to
heat up the heating plate.
A
Art.-No.
Passage
30115
Ø 25 mm
85123
Ø 20 mm
85124
Ø 20 mm
B
RIGHT
WRONG
Temperature pilot lamp
(yellow)
Hole
Branch
Hole
A + E
Ø 20 mm
A + C
A + B
Ø 16 mm
A + C
A + B
Ø 16 mm
A + C
E
D
C
B
A
35
50
60,00
85
and operating lamp
(green)