Gas Connection

• Thread the appliances pressure regulator with 1/2" male
end connection both supplied with this appliance.
• Join the pressure regulator to the entrance threads of the
Gas Manifold with gasket supplied with this appliance.
The regulator is marked with a directional arrow indicating
correct direction of gas flow. Ensure the appliance regulator
is installed with the arrow pointing toward the gas manifold
entrance.
• Connect a manual shut-off valve to the gas supply in an
accessible location for turning on or shutting off gas to the
appliance.
• Install a coupling between the regulator and the shutoff
valve to complete the connection.
• Assure all pipe joint connections are gas tight.
• Check alignment of valves after connecting the cooktop to
the gas supply to be sure the manifold pipe has not been
moved.
FOR ALTERNATIVE PIPING METHODS TO CONNECT THE
APPLIANCE TO THE GAS SUPPLY, A TRAINED SERVICE
TECHNICIAN OR GAS APPLIANCE INSTALLER MUST
MAKE THE GAS SUPPLY CONNECTION. Leak testing of the
appliance shall be conducted by the Installer according to the
Instructions given.
FLARE UNION ADAPTOR
Unless prohibited by local codes or ordinances, a new A.G.A.
- Certified, flexible metal appliance connector may be used to
connect this appliance to its gas supply.
The connector must have an internal diameter not less than
nominal 1/2" NPT pipe and be no more than 5 feet in length.
A 1/2" NPT x 1/2" flare union adapter is required at each
end of the flexible connector.
If a flexible connector is used assure that both the appliance
pressure regulator and manual shut-off valve are joined solidly
to other permanent hard piping (either gas supply or the
appliance manifold) so as to be physically stationary.
Do not attempt to attach the flexible connector directly to an
external pipe thread.
Connection requires flare union adapters.
For Massachusetts Installations:
1. Shut-off valve must be a "T" handle gas valve.
2. Flexible gas connector must not be longer than 36 inches.
3. Not approved for installation in a bedroom or a bathroom
GAS CONNECTION
APPLIANCE PRESSURE REGULATOR
FLARE UNION ADAPTOR
FLEXIBLE APPLIANCE CONNECTOR
(5 FT.) MAX, (1.52 m) MAX
MANIFOLD SHUTOFF VALVES
FLEXIBLE APPLIANCE CONNECTOR
(5 FT.) MAX, (1.52 m) MAX
APPLIANCE PRESSURE REGULATOR
MANIFOLD SHUTOFF VALVES
5 - Gas Requirement
CAUTION
unless unit is direct vent.
EN
13