The surface of the entire back wall above the range and below the hood must be covered with a noncombustible material.
*Consult local code for exact location requirements.
OPENING WIDTH
Rangetop 30"
30"
Rangetop 36"
36"
Note: Clearances from non-combustible materials are not
part of the ANSI Z21.1 scope and not certied.
Clearances to non-combustible materials must
conform with local codes or, in the absence of local
codes, with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54.
Minimum clearances:
Above cooking surface (above 36" [91.4 cm])
• Sides - 6" (15.2 cm)
• Within 6" (15.2 cm) side clearance, wall cabinets no
deeper than 13" (33.0 cm) must be minimum 18" (45.7
cm) above cooking surface
• Wall cabinets directly above product must be a minimum
of 48" (122 cm) above cooking surface.
• Rear - 0" with 9 " backguard; 0" with non-combustible
rear wall.
Below cooking surface (36" [91.4 cm] and below)
• Install with zero clearance between adjacent combustible
construction below the cooking surface and the back
and sides of the appliance.
2 - Product Dimensions and Cutout Requirements
INSTALLATION ON OPEN FRAME
2" (5)
EMPTY SPACE
CUTOUT REQUIREMENTS
A
B
(76.2) 24 1/4 (61.7)
(91.4) 30 3/8 (77.1)
2" (5)
2" (5)
2" (5)
A
ADDITIONAL CLEARANCES:
For island installation, maintain 2-½ in. minimum from
cutout to back edge of countertop and 3 in. minimum from
cutout to side edges of countertop (see top view).
For installation in a stepped island, 12" (30.5 cm) minimum
clearance is required from the back or sides of the rangetop
to a combustible riser.
The island installation is not part of the ANSI Z21.1 scope
and not certified.
FLUSH ISLAND INSTALLATION
BACK
min 3" (7.6)
EN
min 3" (7.6)
7