Symptom
The awning closes even
without any wind
blowing.
The awning motor
does not make its
activation confirmation
movements, when the
shell is snapped onto
the base.
The awning motor
does not make its
confirmation movements
for the "Static Load"
angle memorisation.
WHAT TO DO IF....
Cause
Low batteries.
Problems with radio
communications.
Sensor deactivated.
The sensor was not
able to detect a
stable position.
The sensor detected
a stable position
before being
snapped into place.
*Note: for Wave RX motors manufactured before 01/2013
and TDS Gold control units manufactured before 04/2013
the procedure ends without confirmation movements.
The sensor was not
able to detect an
angle of inclination.
*Note: for Wave RX motors manufactured before 01/2013
and TDS Gold control units manufactured before 04/2013
the procedure ends without confirmation movements.
25
Remedy
Open the sensor shell and
deactivate it: if the LED flashes, the
batteries are almost drained. If the
LED is OFF and it does not come
back on, the batteries are dead.
Change the batteries.
Check that the sensor is not too
far from the motor or the radio
receiver. Change the position of
the sensor.
The sensor is not active. Perform
the activation procedure again.
Check the sensor attachment.
Check that the terminal bar is not
vibrating.
Repeat the activation procedure,
taking care to attach the sensor
within ten seconds of the
confirmation flash.
Repeat the learning procedure.
Check that the angle of inclination
is between 2 and 20 degrees.