3.2.6: CONNECTION:
REMARK: BEFORE CONNECTING THE HOSES, READ THE SAFETY INSTRUCTIONS OF THIS MANUAL
NOTE: The water intake of the CONDENSATION WATER DISSIPATER must be placed a bit lower than the
water outlet level of the CONDENSATION WATER DISSIPATER equipment. The water flow from the Air
Conditioning equipment to the CONDENSATION WATER DISSIPATER should be done by gravity.
Once item 3.2.1 has been carried out (FUNCTION AND DESIGN), lift THE LID of the CONDENSATION
WATER DISSIPATER carefully (4) removing the 2 SIDE SCREWS (5), connect THE OUTLET HOSE OF THE
AIR CONDITIONING EQUIPMENT(19) to the CONNECTOR WATER INTAKE (1) or (2) and connect the hose
to the CONNECTOR (2) or (1) (overflow), once the CONNECTORS (1 and 2) have been installed, put back
THE LID (4) with the SIDE SCREWS OF THE BOX (5)
Next, put the METAL BEARING (6) in the clip at the back of the equipment over the TERMINAL TOP (7)
With these bearings you will hold the equipment and also level the CONDENSATION WATER DISSIPATER on
a horizontal line. This is a necessary condition for the good performance of the equipment.
There are two possible ways of fixing the equipment:
l- It can be fixed to a wall or profile through the hole METAL BEARING has (6)
m- Bend the extremes in V and introduce them in the bearing of the Air Conditioning equipment or available
fixing place. See Graphs l- m

3.3: ELECTRIC CONNECTION:

REMARK: BEFORE MAKING THE ELECTRIC CONNECTION READ THE SAFETY INSTRUCTIONS OF THIS
MANUAL.
3.3.1: Remove the TERMINAL TOP (7) after taking off its SIDE SCREW (8).
3.3.2: To make the connection, use cable with an outdoors protective covering. The connection must be
done in the electric circuit feeding the Air Conditioning equipment, but it must be done before the switch, so
that when the Air Conditioning equipment is turned off, the CONDENSATION WATER DISSIPATER goes on
working to complete the evaporation of all the water left. See Graph k.
Consequently, when the Air Conditioning equipment starts again, (highest electric consumption time) the
CONDENSATION WATER DISSIPATER will not be working.
The connection to the CONDENSATION WATER DISSIPATER must be done through the ELECTRICAL
CONNECTION TERMINAL (9), fastening the cable with the CABLE CLAMP to prevent any mechanical external
event affecting the connection to the ELECTRICAL CONNECTION TERMINAL (9).
Fasten the external cable tidily and safely.
THE CONDENSATION WATER DISSIPATER MUST BE PERMANENTLY CONNECTED TO 110 / 220 V.

4: MAINTENANCE AND CARE:

REMARK: BEFORE DOING ANY MAINTENANCE TASK, READ THE SAFETY INSTRUCTIONS OF THIS MANUAL.
4.1: ELECTRIC DISCONNECTION: DISCONNECT THE CONDENSATION WATER DISSIPATER FROM THE
ELECTRIC CIRCUIT BEFORE HAVING IT SERVICED.
4.2: MAINTENANCE: Once a year, after following item 4.1 (ELECTRICAL DISCONNECTION) or when the
CONDENSATION WATER DISSIPATER needs it, you should take off the DRAIN PLUG (10), and then, the
BLIND PLUG (11), and in case you find some mud and impurities in the CONDENSATION WATER
DISSIPATER, add distilled water through the LOCKING CAP (3) to clean it.
Once clean water flows away again, drain the CONDENSATION WATER DISSIPATER completely, put back
the BLIND PLUG (11) and the DRAIN PLUG (10), tightening them up to avoid any leakage.
4.2.1:GREASE OR IN OIL IN THE METALLIC PAIRS: If for any reason, occasionally or technical, you stain or
impregnates grease or similar the metallic pairs, the CONDENSATION WATER DISSIPATER reduces its
capacity to evaporation. If this happened, before connecting the CONDENSATION WATER DISSIPATER in
the Air Conditioning, make evaporate demineralized water (about 20 cc per minute) for 30 minutes, the
CONDENSATION WATER DISSIPATER will autoclean it and get the efficiency for which it was designed .
After this clean-up operation, proceed to the normal installation.