1. Overview and Features
1.2.7 Battery Voltage (LED 5-8)
LED 5-8 indicate the battery capacity as detailed in the following table:
Battery Voltage
25%
50%
75%
100%
1.2.8 Voltage Setting (Switch 1-3)*
Switch
DC-to-AC Transfer Delay (Switch 1)
Low Battery Alarm (Switch 2)
AC Transfer Voltage (Switch 3)
* Notes:
1. Switches are located farthest from the battery temperature port. See diagram on page 3.
2. The switches must be set before the system is turned on.
3. Switch 2 sets the low battery voltage alarm level (at higher voltage setting, alarm will sound sooner).
4. Switch 3 sets the low-level AC-to-DC voltage point. If the AC input voltage decreases to below the setpoint, the inverter will
automatically switch to DC MODE. See the following table for details.
Nominal Voltage
On
230V
Off
1.2.9 Search Mode Setting (Switch 4)
Search Mode activates when the unit is operating in inverter mode (battery power) to prevent unnecessary battery discharge
when electrical power is not required. If the inverter is supporting loads that must constantly be powered, turn off switch 4 to
disable Search Mode.
Switch 4
ON
OFF (Default)
1.2.10 Floating Voltage/Battery Type (Switch 5)
Switch 5
ON (Default)
OFF
Note: The unit will charge the battery to acceptance voltage, continue for 1 to 12 hours, then drop to floating voltage.
201110117 93-3054.indb 5
LED 5
On
On
On
On
Low Voltage Transfer Point (AC-to-DC)
190
170
Floating Voltage
13.8V
13.2V
LED 6
On
On
On
ON
30 sec (Default)
11.2V
190V
Return Voltage Point (DC-to-AC)
Search Mode
Enable
Disable
Acceptance Voltage
14.5V
13.8V
5
LED 7
LED 8
On
On
On
OFF
5 sec
10.9V (Default)
170V (Default)
200
180
Function
Inverter turns on only if load is >100W
Inverter always on if AC power is absent
Battery Type
Absorbed Glass Mat (AGM)
Wet-Cell