Model
Article no.
DC
Charge voltage BULK (25°C)
Charge voltage ABSORPTION (25°C)
Charge voltage FLOAT
(Wet; 25°C)
Charge voltage FLOAT
(Gel; 25°C)
Total charge current
DC consumption with connected battery
Number of outlets
Charge characteristics
Absorption time, reduced output
Temperature compensation
Voltage compensation
Recommended DC fuse (Main)
Recommended DC fuse (Slave)
Recommended Wire size < 1.5m
Recommended Wire size > 1.5m
Recommended battery capacity
AC
Input voltage range
Frequency
Full load consumption (230VAC)
AC cable
Power factor / cos phi
General
Ambient operating temperature
Storage temperature
Operating humidity
Efficiency
Cooling
Protections
Short circuiting
Over heating
Protection degree
Options
Communication
Suitable as power supply without battery
Mechanical
Connections input/output
Dimensions (HxWxD)
Mounting holes
Weight
Cabinet
Directives:
Set points software
Max. bulk/abs time
Return amps
Abs voltage
Float voltage
Forced to float
SPECIFICATIONS IVO SMART
IVO Smart 12/35-3
43013500
14.40VDC
14.25VDC
13.25VDC
13.80VDC
35A
<10mA
2 main outputs + 1 slave 3A
IUoUo / 3 stage / automatic / DIN 41772
Maximal 6 hours (adjustable); minimal 15 minutes
30mV/°C
Auto sense
50A-T
5A-T
6mm²/AWG9
10mm²/AWG7
70~250Ah
180~250VAC (90~140VAC)
50/60Hz
550VA
3x0.75 mm²
0.99
Guaranteed operation: 0°C to 60°C / 32° F to 140° F (derating above 40°C /
104°F, 5% per °C); in practice: -20°C to 60°C / -4°F to 140°F.
-25°C to 85°C / -13°F to 185°F
95% max., non-condensing
90% (at nominal input voltage)
Variofan 'low noise' <54dBA
Yes
Limited power by temperature sense circuit
Horizontally mounted: IP21, vertically mounted: IP20
Quasi RS232, modular RJ12 connection, to alter set points and to change
characteristics (optional interface required) or to connect a temperature sensor
and/or remote panel.
Yes, in the Forced float mode.
Screw terminals, maximum wire size 25 mm² / AWG 3
313 x 187 x 82 mm; 12.3 x 7.4 x 3.2 inch
Diameter 5mm
3.4 kg / 7.5 lbs
Anodized aluminium, strapton ABS blend, blue RAL 5021
- Generic emission and disturbances standard: EN 55014-1:1993
- Generic harmonic current emissions: EN61000-3-3:1995
- Generic & safety accreditations immunity standard: EN55014-2: 1997
- Electrostatic discharge : EN61000-4-2:1995
- Electrical fast transients: EN61000-4-4:1995
- Surge transient: EN61000-4-5:1995
- Conducted radio frequency disturbances: EN61000-4-6:1996
- Voltage dips: EN61000-4-11:1994
Default setting
360min.
2/16 of I-max
14.25/28.50VDC
13.25/26.50VDC
13.80/27.60VDC
IVO Smart 12/50-3
43015000
14.40VDC
14.25VDC
13.25VDC
13.80VDC
50A
<10mA
30mV/°C
80A-T
5A-T
10mm²/AWG7
16mm²/AWG5
100~350Ah
800VA
Set points software
Gel voltage setting
Diode compensation setting
DC alarm voltage
DC alarm delay
IVO Smart 24/15-3
43021530
28.80VDC
28.50VDC
26.50VDC
27.60VDC
15A
<5mA
60mV/°C
25A-T
5A-T
4mm²/AWG11
6mm²/AWG9
30~125Ah
480VA
Default setting
550mV
600mV
12.50/25.00VDC
30s
loading

Este manual también es adecuado para:

Ivo smart 12/50-3Ivo smart 24/15-3