CPX-FVDA-P...
–
Operation in CPX valve terminals is only permitted with CPX valve terminals
with VTSA pneumatics, type 44 and type 45.
–
A maximum of one output module CPX-FVDA-P may be used for each CPX ter-
minal or CPX valve terminal.
–
The output module CPX-FVDA-P may only be installed directly adjacent to the
pneumatic interface for VTSA pneumatics or the right end plate.
–
Only the following components are permitted when assembling the module:
– Interlinking block CPX-M-GE-EV-FVO
– Connection block CPX-M-4-M12X2-5POL.
Foreseeable misuse
Foreseeable misuse includes:
–
Use outdoors
–
Use in non-industrial applications
–
Use outside the product limits defined in the technical data
–
Unauthorised modifications
–
Use in conjunction with loads with which disconnection can result in hazard-
ous movements or conditions
Note
Assembling the output module CPX-FVDA-P with connection and interlinking
blocks not specified here is not permitted.
It is not permitted to use the module in:
A CPX terminal fitted with a CPX-FEC
–
A CPX terminal fitted with a CPX-CEC
–
A CPX valve terminal with pneumatics not of type VTSA
–
A CPX terminal version P.
–
Repairs to the module are not permitted. Unauthorised repairs void the certific-
ation of the module.