EtherNet/IP Protocol
The PanelView terminal is initially set to DHCP with BootP support (Dynamic Host
Configuration Protocol) enabled. If your network has a DHCP/BootP server, you
can connect the PanelView terminal to the EtherNet/IP network and the
DHCP/BootP server will automatically establish an IP address. If your network does
not have a DHCP/BootP server, you need to program an IP address. This is done by
accessing Configuration Mode on the PanelView terminal and selecting
Communication Setup. For details, refer to the PanelView Standard Operator
Terminals Manual.
If a PanelView is connected to an EtherNet/IP network and has
IMPORTANT
the same IP address as another device on the network, both
devices will drop off the network.
ControlNet Protocol
When making ControlNet connections, only use the PanelView
IMPORTANT
Channel B for redundant communications. Connecting Channel B
to a Channel A only ControlNet network will result in:
• the PanelView not being able to communicate over the
network
• a PanelView communicatons fault after several minutes
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
PanelView 550 Terminals
13
Publication 2711-IN009D-MU-P