General Safety Notes; Assembly And Commissioning - Maico DZQ Serie Instrucciones De Montaje Y Modo De Empleo

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 21
High performance axial fans
for use in potentially explosive
atmospheres
Wall fans
DZQ ../. B E Ex e
DZS ../. B E Ex e
Duct fans
DZR ../. B E Ex e
Roof fans
DZD ../. B E Ex e
Area of use and operating characteristics
(intended use)
The device has been manufactured according
to directive 94/9/EC.
The fan fulfils the requirements of directive 94/9/
EC for equipment and protective systems in areas
subject to explosion hazards. Our EC-Conformity
Declaration accompanies this manual.
Areas subject to explosion hazards
The fan is classified in group II, category 2G;
therefore, it is suitable for use in areas subject to
explosion hazards of zones 1 and 2. It is particularly
suitable for suctioning explosive mixtures out of
workspaces of zone 1.
Temperatures
Permitted ambient and airstream temperature:
- 20 °C to T
(for T
amb
Minimum ignition temperature of a potentially explo-
sive atmosphere: determined by temperature class
T.. (see the rating plate).
Adjustable airflow volume of the fan
The speed of the fan can be reduced by lowering
the motor terminal voltage below the rated voltage
U
. The voltage may be lowered only for the fan's
N
supply frequency. Use a transformer for this. Use
with frequency converters is not permitted. The
speed of fans where U
cannot be adjusted.
Deviation for the fan types DZ. 35/2 B E Ex e:
The airflow volume of the fan is not adjustable
The fan may be used only with the voltage U
indicated on the rating plate. The speed of the fan
must not be reduced by lowering the motor
terminal voltage below the rated voltage U
Thermal motor protection
The temperature in the fan motor is monitored by
PTC thermistors. The PTC thermistors (terminals 5
and 6 on the terminal box; Fig. 2) must be connected
to an activation system (safety equipment according
to directive 94/9/EC) that continuously disconnects
the fan from power if the temperature is too high.
We recommend the use of the MAICO MVS 6
thermistor-type motor protection system, which is to
, see the rating plate)
amb
< 400 V (special models)
N
– Subject to change ! –
be mounted outside of the areas subject to
explosion hazards (label II (2) G).
Parallel operation of several fans on a single
activation system is not permitted.
The fan may not be used if solid or liquid materials,
such as paint particles from painting equipment,
can be deposited on the motor.

General safety notes

Read the complete instructions carefully before you
mount the fan and put it into operation.
Storing the instructions
After assembly, store the instructions of each fan. A
copy of the rating plate can be found on the rear of
the operating instructions. The serial number is
located at the bottom right corner of the rating plate.
Obligations of the assembler and the operator
We would like to point out that additional safety
regulations, such as directive 1999/92/EC and
national regulations regarding the prevention of
accidents, must be maintained when assembling
and operating the fan.
During assembly, heed the valid installation
regulations, e.g. VDE 0100 and EN 60079-14.
MAICO accepts no liability for damages caused by
non-authorised use.

Assembly and commissioning

Assembly and commissioning may be carried out
only by skilled electricians trained in explosion
protection.
The rotating fan parts have been adjusted at the
factory. Therefore, the device may not be
disassembled. The temporary removal of the termi-
nal box lid during the installation of the device is not
subject to this limitation.
For wall fans DZQ and DZS only:
The fan may be attached only to level walls or
N
ceiling surfaces to prevent strain on the wall plate
(DZQ) or the wall ring (DZS).
Before commissioning the fan, the air gap between
.
N
the impeller and the wall plate/ring must be checked
(Fig. 1). It must meet the minimum values according
to Tab. 1 over the entire circumference. Use the
air-gap gauge that is included with the device.
5