Installation
Wiring
1
L
1
3
G
Wiring
Connect the power wires to the switch terminals and connect
the ground wire to the ground terminal block inside the
enclosure. Reference the National Electric Code and all local
codes for appropriate wire size and grounding requirements.
See chapter Cabling.
All cables must have 167 °F / 75 °C minimum rating.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
See general safety instructions on page 1/2 before proceeding.
Failure to follow these instructions will result in death or serious injury.
1/12 Installation | Instruction Bulletin EOHU361/2/3JK/RK/S/SS, 1SCC340036M1401 / A
Safety
switch
Incoming and
size [A]
outgoing terminal lugs
Wire range
ALL
#14 - 2/0
2.5 - 70 mm
2
Wire strip length L
ALL
0.55 - 0.63 in
14 - 16 mm
Wire tightening torque for
Cu and Al cables (wire size)
[lbs.in (#)]
[Nm (mm
30
35 (#14 - 10)
3.9 (2.5 - 4)
40 (#8)
4.5 (6)
60
45 (#6 - 4)
5.1 (10 - 16)
100
50 (#3 - 2/0)
5.6 (25 - 70)
Ground bus
#14 - 2
2.5 - 35 mm
2
0.39 - 0.47 in
10 - 11.9 mm
Wire size / tightening torque
)]
[# / lbs.in]
[mm
/ Nm]
2
2
8 / 40
6 / 4.5
6 / 45
10 / 5.1
8 / 40
6 / 4.5
6 / 45
10 / 5.1
4 / 45
16 / 5.1
2