Setting and using method
n Temperature tracking function in thermostat mode
: periodically make a target temp. based on indoor temp. from IDU and delta value and transfer a
renewal target temp. value to IDU.
SETTING_SW
Function
SW 1
Universal Input
SW 2
Universal Input Type
SW 3
Temperature Tracking
SW 4
-
SW 5
Tracking delta Temperature
SW 6
SW 7
Tracking Period Time
SW 8
Notes
• The Set value of Fahrenheit temperature is twice the set value of Celsius Temperature.
• New Target temperature in Cooling Opreation = Room temperature - Tracking delta temperature
• New Target temperature in Heating Operation = Room temperature + Tracking delta temperature
n Operation example
: When set offset value to ±6 ℉ (±3 ℃), period time value to 3 minutes.
Period 1
Period 2
(3 minutes)
(3 minutes)
Thermostat
Cooling on
Cooling off
Operation
IDU off
IDU Operation
Cooling
or Fan mode
Indoor Room
70 ℉(21 ℃)
72 ℉(22 ℃)
Temperature
Target
Updated to
Not update
Temperature
64 ℉(18 ℃)
20 Dry contact for thermostat
Off
On
Disable
Enable
Voltage
Resistance
Disable
Enable
-
-
SW 5
SW 6
SET VALUE
OFF
OFF
±8 ℉ (±4 ℃)
ON
OFF
±6 ℉ (±3 ℃)
OFF
ON
±4 ℉ (±2 ℃)
ON
ON
±2 ℉ (±1 ℃)
SW 7
SW 8
SET VALUE
OFF
OFF
3 minutes
ON
OFF
5 minutes
OFF
ON
10 minutes
ON
ON
20 minutes
Period 3
Period 4
Period 5
(3 minutes)
(3 minutes)
(3 minutes)
Heating on
Heating off
Fan only
IDU off
Heating
Fan mode
or Fan mode
64 ℉(18 ℃)
80 ℉(27 ℃)
Don't care
Update to
Not update
Not update
70 ℉(21 ℃)
Indoor unit monitoring
n Monitoring whether the indoor unit is operating: Refer to
below and connect to the control device that you want to
control.
n Monitoring indoor unit error: Refer to below and connect to
the control device that you want to control.
!
CAUTION
Field supply power should not use more than DC 12 V (0.5 A), AC 24 V (0.5 A).
Setting and using method
Field Supply
Power
Operation Display
AC or DC
(Depends on Operation display power type)
Field Supply
Power
Error Display
AC or DC
(Depends on Error display power type)
Installation manual 21