Installation
Caution:
To ensure correct operation of your system, you
must follow the recommended cabling practices described
below.
Wiring
Connect the detector base as shown in Figure 1:
1.
PIN 1 Positive line
2.
PIN 2 Data line
3.
PIN 3 Negative line
The cable used should:
Have a cross-sectional area of at least 1.5 mm
Have maximum resistance of 13.3 Ω/km per core
Detector placement
Detectors should be installed above the level at which the gas
is generated.
Note: Installing the detectors too high or placing the detectors
too close to windows, air inlets or ventilation systems may
prevent the carbon monoxide from reaching the detector.
Detector installation
Insert the detector head into the base, rotating it clockwise until
it clicks into place.
The detector head can be locked into the base by breaking the
locking tab at the base of the detector head (Figure 2, item 1).
To remove a locked detector, insert a screwdriver into the base
slot and push.
LED indications
When in service the detector LED will flash green. A flashing
red LED indicates a fault. A steady red LED indicates an alarm
(by default this occurs when CO levels of 50 ppm or higher are
detected).
Maintenance
Basic maintenance consists of a yearly inspection. Do not
modify the internal wiring or circuitry.
Specifications
Operating voltage
Current consumption
Standby (LED off)
Alarm (red LED illuminated)
LED indications
Standby
Fault
Alarm (50 PPM)
Detector uncalibrated
2 / 8
2
10 to 20 VDC
6 mA
15 mA
Flashing green LED every 15 s
Flashing red LED every 15 s
Steady red LED
Flashing red LED every 2 s
Accuracy
0 to 50 ppm
50 to 300 ppm
CO detection range
IP rating
Maximum number of detectors per
zone
Operating temperature
Storage temperature
Relative humidity
Dimensions (Ø x H)
Weight
Regulatory information
Manufacturer
United Technologies Safety System Co. Ltd.
80, Changjiang East Road,
QETDZ, Qinhuangdao,
Hebei Province, China 066004
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
Year of
The first two digits of the product serial number
manufacture
(located on the product identification label)
indicate the year of manufacture.
Certification
09
Year of first CE
marking
LOM certificate
09MOGA3101
Compliance
UNE 23300:1984 +1M:2005
2012/19/EU (WEEE directive): Products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper recycling, return this product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information see:
www.recyclethis.info.
Contact information
For contact information, see www.utcfssecurityproducts.eu.
ES: Instrucciones de instalación
Descripción
Este documento incluye información de instalación para el
detector de monóxido de carbono KMD300 de UTC Fire &
Security.
El modelo KMD300 está diseñado para su uso con los
sistemas de detección de CO KM300 y KM260.
La vida útil del detector KMD300 es de cinco
Principio de operación
Detección basada en sensor electroquímico que mejora la
exactitud de la medida y reduce el consumo, con
compensación térmica integrada, y control basado en
microcontrolador de 16 bits.
P/N 10-4101-501-2KM3-07 • ISS 16JAN17
± 5 ppm
5% of measured value
0 to 300 ppm
IP42
15
−10 to +40°C
−10 to +70ºC
10 to 95% noncondensing
124 x 62 mm
300 g