Johnson Controls York AS1 Instrucciones De Instalación página 8

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 1
Table of temperatures
The following table indicates the ratio be-
tween the temperature, heater and voltage.
Temperature °C
-5
-4
-3
-2
-1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
Troubleshooting
Code
91
92
93
94
95
96
97
98
99
All data and dimensions are subject to change without prior notice.
8
15KOhm ambient probe: DPC-1 and
DPC-1R thermostats, ambient remote probe
NTC value
57 382
54 657
52 077
49 633
47 317
45 122
43 041
41 068
39 196
37 419
35 733
34 132
32 612
31 167
29 795
28 490
27 250
26 070
24 947
23 880
22 863
21 895
20 974
20 096
19 259
18 462
17 702
16 978
16 287
15 627
14 998
14 398
13 824
13 277
12 754
12 254
11 777
11 321
10 884
10 467
10 068
9 686
9 321
8 971
8 636
8 316
8 009
7 715
7 433
7 163
6 904
6 656
6 418
6 189
5 970
5 760
GB
(RS-1), duct remote probe (DS-1) and aver-
age probe (AS-1).
Description
Ambient probe open or in short circuit
Internal probe not calibrated
Communication error
Failure with terminal AL connected
Digital probe S5 not detected
Digital probe S6 not detected
Digital probe S7 not detected
Digital probe S8 not detected
Outdoor digital probe not detected
Voltage
0.445
0.464
0.483
0.503
0.523
0.544
0.566
0.587
0.610
0.633
0.656
0.680
0.704
0.729
0.754
0.779
0.805
0.832
0.858
0.885
0.913
0.941
0.969
0.997
1.025
1.054
1.083
1.112
1.141
1.171
1.200
1.230
1.259
1.289
1.318
1.348
1.378
1.407
1.436
1.466
1.495
1.524
1.553
1.581
1.610
1.638
1.666
1.694
1.721
1.748
1.775
1.801
1.827
1.853
1.878
1.904
Tabla de contenido