INSTALLATION AND MAINTENANCE INSTRuCTIONS
NFXI-MM10
Ten Input Monitor Module
SPECIFICATIONS
Normal Operating Voltage:
Stand-By Current:
Alarm Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Wire Gauge:
Maximum SLC Wiring Resistance:
Maximum IDC Wiring Resistance:
Maximum IDC Voltage:
Maximum IDC Current:
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the appropriate control panel installation manual for detailed system infor-
mation. If the modules will be installed in an existing operational system,
inform the operator and local authority that the system will be temporarily
out of service. Disconnect the power to the control panel before installing the
modules. This system contains static sensitive components. Always ground
yourself with a proper wrist strap before handling any circuits so that static
charges are removed from the body. The housing cabinet should be metallic
and suitably grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
This manual refers only to installations conforming to EN54 requirements.
GENERAL DESCRIPTION
The NFXI-MM10 Ten Input Monitor Module is intended for use in an intel-
ligent alarm system. Each monitor module is intended to interface between a
control panel and normally open contact devices, such as pull stations. A com-
mon SLC input is used for all modules, and the initiating device loops share
a common supervisory supply and ground. Otherwise, each monitor operates
independently from the others.
Each module also has panel controlled tri-color (green, red and amber)
LED indicators. The panel can cause the LEDs to blink, latch on, or latch off.
The module also provides short circuit isolators to prevent shorts on the fire
detection and alarm system loop from disabling more than one device on the
intelligent loop.
ADDRESSES
In systems using CLIP (Communication Loop Intelligent Protocol) a pair of
rotary code switches is used to set the address of the first module from 01 to
90. The remaining modules are automatically assigned to the next nine higher
addresses. Provisions are included for disabling a maximum of six unused
modules to release the addresses for use elsewhere.
In systems using Advanced Protocol a pair of rotary code switches is used to
set the address of the module from 01 to 159. Only one address is used for the
entire multi-module with sub-addresses completing the remaining addresses.
INCLuDED:
(6) 1 x 4 Terminal Blocks
(4) Screws
NO-460-023
15-29 VDC
3.5 mA
60 mA (assumes all ten LEDs solid on)
–10°C to 55°C
10 to 93% Non condensing
17.3cm H x 14.7cm W x 3.2cm D
Suitably grounded metallic cabinet
0.8 mm 2 - 3.25mm 2
40 Ohms
40 Ohms
12 VDC
1 mA
(2) 3.2 cm Stand offs
(2) Nuts
(10) 47k Ohm
End of Line Resistors
COMPATIBILITY REQuIREMENTS
To ensure proper operation, this module shall be connected to a listed compat-
ible system control panel.
In order to comply with EN54-17 and EN54-18 requirements the modules
must be installed within a grounded, metal enclosure that is suitable for the
application. The CE marking label confirms compliance with CPD, and must
be applied to the module enclosure only once installation of the module in the
enclosure is completed. The label shall be mounted in a position that is visible
during installation and accessible during maintenance. The label shall not be
placed on screws or other easily removable parts.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2.
All wiring to the NFXI-MM10 is done via terminal blocks. In order to prop-
erly make electrical connections strip approximately .6 cm of insulation
from the end of wire, sliding the bare end of the wire under the clamping
plate screw.
3.
Set the address on the modules per the job drawing. Use the rotary code
switches to set the address of the module. (refer to Addresses section)
NOTE: In CLIP the remaining modules are automatically assigned to the next
nine higher addresses. For example, if the base address switch is set to 28, the
next nine modules will be addressed to 29, 30, 31, 32, 33, 34, 35, 36, and 37.
DO NOT set the lowest address above 90, as the other modules will be as-
signed to nonexistent addresses.
4.
A dip switch is provided to disable a maximum of six unused modules
in CLIP. Modules are disabled from the highest address and work down-
ward. If two modules are disabled, the lowest eight addresses will be
functional, while the highest two will be disabled. For example, if the
dip switch is set to disable two addresses and the base code wheel is set
to 28, the modules will be assigned to 28, 29, 30, 31, 32, 33, 34 and 35
while disabling the highest two positions.
1
Notifier by Honeywell.
Charles Avenue Burgess Hill
West Sussex RH15 9UF UK
I56-3976-001
loading

Resumen de contenidos para Honeywell Notifier NFXI-MM10

  • Página 1 INSTALLATION AND MAINTENANCE INSTRuCTIONS NFXI-MM10 Notifier by Honeywell. Ten Input Monitor Module Charles Avenue Burgess Hill West Sussex RH15 9UF UK SPECIFICATIONS Normal Operating Voltage: 15-29 VDC Stand-By Current: 3.5 mA Alarm Current: 60 mA (assumes all ten LEDs solid on) Temperature Range: –10°C to 55°C...
  • Página 2 FIGuRE 1: TYPICAL INITIATING DEvICE CIRCuIT CONFIGuRATION COMMUNICATION TWISTED PAIR IS COMMUNICATION LINE 29 VDC MAX. TWISTED PAIR IS RECOMMENDED. TO NEXT DEVICE FROM PANEL OR PREVIOUS DEVICE POWER LIMITED AND SUPERVISED POWER L CLASS B IDC (TYPICAL) AND SUPE STATUS INDICATORS CLASS B...
  • Página 3 ISTRuZIONI DI INSTALLAZIONE E MANuTENZIONE NFXI-MM10 Notifier by Honeywell. Modulo di controllo a dieci ingressi Charles Avenue Burgess Hill West Sussex RH15 9UF UK SPECIFIChE Tensione normale di esercizio: 15-29 VDC Corrente di riserva: 3,5 mA Corrente di allarme: 60 mA (a condizione che tutti e dieci i LED siano accesi) Intervallo di temperatura: da -10°...
  • Página 4 FIGuRA 1: CONFIGuRAZIONE TIPICA DEL CIRCuITO DEL DISPOSITIvO DI ATTIvAZIONE LINEA DI COMUNIC SI CONSIGLIA LINEA DI COMUNICAZIONE MAX. 29 VDC SI CONSIGLIA UN DOPPINO. AL DISPOSITIVO SUCCESSIVO DAL PANNELLO O DAL DISPOSITIVO PRECEDENTE INDICATORI DI STATO INDICATORI D CLASSE B IDC (TIPICA) CONTROLLATI E CON 47 K...
  • Página 5: Módulo De Supervisión De Diez Entradas

    INSTRuCCIONES DE INSTALACIÓN Y MANTENIMIENTO NFXI-MM10 Notifier by Honeywell. Módulo de supervisión de diez entradas Charles Avenue Burgess Hill West Sussex RH15 9UF UK ESPECIFICACIONES Tensión operativa normal: de 15 a 29 VCC Corriente en espera: 3,5 mA Corriente de alarma:...
  • Página 6 FIGuRA 1: CONFIGuRACIÓN hABITuAL DEL CIRCuITO DEL DISPOSITIvO DE INICIACIÓN LÍNEA DE COMUNICAC SE RECOMIENDA LÍNEA DE COMUNICACIONES 29 VCC MÁX. SE RECOMIENDA PAR TRENZADO. AL DISPOSITIVO SIGUIENTE DESDE EL PANEL O DISPOSITIVO ANTERIOR SUPERVISADO Y CON LIMITACIÓN DE POTENCIA CC DE ENTRADA DE CLASE B (TÍPICO) SUPERVISADO LIMITACIÓN DE P...
  • Página 7 INSTALLATIONS- uND WARTuNGSANLEITuNG NFXI-MM10 Notifier by Honeywell. Überwachungsmodul mit zehn Eingängen Charles Avenue Burgess Hill West Sussex RH15 9UF UK SPEZIFIKATION Betriebsspannungsbereich: 15 – 29 V DC Ruhestrom: 3,5 mA Alarmstrom: 60 mA (bei zehn dauerleuchtenden LEDs) Temperaturbereich: -10 °C bis 55 °C...
  • Página 8 ABBILDuNG 1: TYPISChE SChALTuNGSANORDNuNG EINER MELDEvORRIChTuNG KOMMUNIKATIONSLEITU GEDRILLTES LEITERPA KOMMUNIKATIONSLEITUNG, MAX. 29 V DC GEDRILLTES LEITERPAAR EMPFOHLEN ZUR NÄCHSTEN VORRICHTUNG VON DER ZENTRALE ODER DER VORANGEGANGENEN VORRICHTUNG BEGRENZTE UND ÜBERWACHTE SPANNUNG IDC DER KLASSE B (TYPISCH) BEGRENZTE U ÜBERWACHTE SPA 47 K STATUSANZEIGEN EOL-WIDERST...