WIRING DIAGRAM
LOWER HOUSING
HEATSINK
G
GREEN/YELLOW
G
G
(GREEN/
YELLOW)
3 POLE SPLICE
CONNECTOR
DRIVER
(YELLOW/BLACK)
P1 -
LED PCB 1
P4 +
LINE
NEUTRAL
POSITIVE
NEGATIVE
GROUND
105°
45°
60°
Ex IIG Ex ec IIcT* GC
3.
Re-install back cover/heat sink and tighten all nine (9) mounting screws to 22 in.-
lbs. (2.5 N-m). Be sure wires are not pinched during cover installation.
•
Replace any damaged or missing cover screws. Use only stainless steel
#10-24 x 0.75"cover screws.
4.
To make final vertical adjustment, loosen the pivot bolts on the floodlight yoke to
position floodlight at the desired angle. See Figure 3.
NOTE: Yoke mounting range is 45 degrees back to 60 degrees forward.
5.
Rotate the floodlight housing to the desired position.
6.
Tighten the two (2) 1/2-13 pivot bolts to 45 ft-lbs. (61 N-m).
7.
Tighten two (2) 5/16-18 angle marker bolts to 138 in.-lbs. (15.6 N-m).
8.
Turn power on.
To avoid ignition of the hazardous atmospheres or overheating of the
floodlight:
Do not position the floodlight beyond the aiming range limits.
IF 1846 • 03/19
SUPPLY WIRE
N
L
BLACK
2X
WHITE
(DC-)
(DC+)
3 POLE SPLICE
CONNECTOR
N
L
N
L
(WHITE)
(BLACK)
INPUT
BLACK/WHITE
PURPLE (+)
GRAY (-)
DIMMING LEADS
OUTPUT
0-10 VDC SIGNAL
10V = 100% LIGHT OUTPUT
+ (RED)
- (BLUE)
2X
(YELLOW/RED)
2 POLE SPLICE
CONNECTOR
60°
Ex IID Ex tb IIcT* Db
PIVOT
1/2-13 BOLT
Figure 3
5/16-18 ANGLE BOLT
Figure 3
WARNING
Copyright
GREEN/YELLOW
3X 3 POLE SPLICE
CONNECTOR
3X
2 POLE SPLICE
CONNECTOR
Figure 2
LOOSEN BOLTS TO SET
FLOODLIGHT ANGLE
EXTERNAL GROUND INSTALLATION INSTRUCTIONS
1.
Unscrew the ground lug fastener shown in Figure 4.
2.
Install stripped ground wire (0.5" [12.7mm]) in ground lug.
3.
Torque ground lug fastener down on ground wire. Torque to 25 in.-lbs. [2.82
N-m], as shown in Figure 4.
2019, Eaton's Crouse-Hinds Division
®
HEATSINK
OPEN TERMINALS FOR THRU WIRING
FROM FIXTURE TO FIXTURE
WHITE
BLACK
(DC+)
(DC-)
G
N
G
N
(GREEN/
(WHITE)
YELLOW)
INPUT
DRIVER
OUTPUT
+ (RED)
- (BLUE)
(YELLOW/BLACK)
(YELLOW/RED)
P1 -
LED PCB 1
P4 +
B
Input wire location
Input wire location
Ground lug location
(torque to 25 in-lbs
Ground Lug Location
(Torque to 25 in.-lbs.)
[2.82 N-m])
Figure 4
UPPER HOUSING
3X
2 POLE SPLICE
CONNECTOR
L
L
(BLACK)
BLACK/WHITE
PURPLE (+)
GRAY (-)
DIMMING LEADS
0-10 VDC SIGNAL
10V = 100% LIGHT OUTPUT
2X
2 POLE SPLICE
CONNECTOR
Mounting
screw
Mounting Screw
(torque to
(Torque to 19 in.-lbs.)
19 in.-lbs.
[2.15 N-m])
Page 2