4. CONNECTORS DESCRIPTION
XC30 Connector: Analog and Digital Outputs
-
+
(*)
+
-
RL ≥ 500 Ω
(*) The internal 24Vdc power supply can be used by connecting XC30:9 to XC31:5 and XC31:4 to the
load.
4
XC30
1
AO101 ( V ) Analog output 101 in voltage
2
AO101 ( I ) Analog output 101 in current
0 V reference for analog
3
AGND
output
4
AO102 ( V ) Analog output 102 in voltage
5
AO102 ( I ) Analog output 102 in current
0 V reference for analog
6
AGND
output
7
NC
Not connected
8
NC
Not connected
Common to digital outputs
9
COM DO
DO104, DO105 and DO106
10
NA101
Digital relay outputs DO101
11
C101
12
NA102
Digital relay outputs DO102
13
C102
14
NA103
Digital relay outputs DO103
15
C103
16
DO104
Bidirectional opto-isolated
17
DO105
digital outputs
18
DO106
Figure 5: Description of XC30 connector
Function
(-10 to +10) V / (0 to +10) V
Resolution: 12 bits
RL ≥ 10 kΩ
(0 to 20) mA / (4 to 20) mA
Resolution: 12 bits
RL ≤ 500 Ω
(-10 to +10) V / (0 to +10) V
Resolution: 12 bits
RL ≥ 10 kΩ
(0 to 20) mA / (4 to 20) mA
Resolution: 12 bits
RL ≤ 500 Ω
Contact capacity:
Maximum voltage:: 250 VAC
Maximum current : 3 A
NO – Normally open;
C – Common.
Maximum voltage: 24 VDC
Maximum current : 500 mA
Specifications
-
-
-
-
-