The Parameter Menu Par - Technische Alternative ESR 31 Manual De Instrucciones

Ocultar thumbs Ver también para ESR 31:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

English
The parameter menu
(Version number, program number, min, max, diff, auto/manual mode)
Once the parameter menu has been opened (using the code 32), the following tips and
setting options appear depending on the program selected:
VR 3.1
Software version of the device (VR = version with relay output, VD = speed ver-
sion). It cannot be changed as it indicates the intelligence of the device and must
be provided if there are any queries.
PR
Selection of the appropriate program according to the selected diagram. For a
solar thermal system, that would be the number 0.
The device does not have any switching differentials (difference between temperatures to
switch on or off); rather, all of the threshold values are divided into switch-on and switch-off
values. In addition, some programs have several similar thresholds such as max, max2. To
make a distinction, the index for max is also displayed in the same line.
CAUTION: When setting the parameter, the computer always limits the threshold value (such
as max on) when it approaches a certain temperature of the second threshold (such as
max off) to prevent negative hysteresis. If a threshold cannot be changed any longer, the
second threshold has to be changed first.
max When this temperature has been reached, the output is blocked (ex works = 65°C).
max The output blocked at max  is released again when this temperature has been
reached. max generally serves to limit storage. Recommendation: The switch-off
point should be some 3-5K higher than the switch-on point in the storage area and
some 1-2K higher than in the pool area. The software does not allow for differences
less than 1K (ex works = 60°C).
min  When this temperature has been reached at the sensor, the output is released
(display only with the corresponding program diagram) (ex works = 5°C).
min  The output previously released via min  is blocked again when this temperature
has been reached. min generally protects the boilers from soot. Recommendation:
The switch-on point should be some 3-5K higher than the switch-off point. The
software does not allow for differences less than 1K (ex works = 0°C).
diff  If the temperature difference between the two set sensors surpasses this value, the
output is released. For most programs, diff is the basic function (differential control-
ler) of the system. Recommendation: For solar applications, diff should be set
to around 7-10K (ex works = 8K). Slightly lower values suffice for the loading pump
program.
diff  The output previously released when diff  was reached is blocked again when
this temperature difference is reached(ex works = 8K). Recommendation: diff 
should be set to around 3-5K (ex works = 4K). Although the software allows for a
minimum difference of 0.1K between the switch-on and switch-off points, no value
less than 2K can be entered for sensor and measurement tolerance.
O AUTO The output is set to automatic mode and can be switched for test purposes to man-
ual mode (O ON, O OFF). When the manual mode has been selected, an icon ap-
pears at the top. If the hand symbol is displayed, the control function is deac-
tivated.
C AUTO The control output is set to automatic mode and can be switched for test purposes
to manual mode (C ON, C OFF). When the manual mode has been selected, an
icon appears at the top. If the hand symbol is displayed, the control function
is deactivated.
14
PAR
Tabla de contenido
loading

Tabla de contenido