English
• Only transport the product on the pallet and
only use approved handling equipment.
• Make sure the product is stable in transit.
• Prior to installation, store the product on the
pallet so that it remains dry and is protected
from the sun.
4 Use as intended
The Wilo DrainLift WS625 is used in combination
with a submersible pump as a pump station for
domestic sewage that is both free of faeces and
contains faeces in accordance with EN 12056-1. It
is used to drain drainage points in buildings and on
sites below the backflow level, where sewage
cannot drain into the public drains with a natural
gradient.
WARNING! Health hazard!
Because of the materials used, this product is
not suitable for supplying drinking water! Con-
taminated sewage is a health hazard. Do not use
the pump station inside buildings.
5.2

Technical data

max. admissible pressure in the
pressure pipe:
Pressure pipe connection
Inflow connection
Ventilation connection / cable bushing
max. admissible ambient temperature:
max. admissible groundwater level:
Storage volume
Suitable pump types
Suitable Wilo shaft cover
5.3 Dimensions
The main dimensions are shown in mm on the
dimension drawing (Fig. 1) - for further informa-
tion, see data sheet/catalogue
Type
WS 625 E / 1200
WS 625 E / 1500
WS 625 E / 1800
WS 625 E / 2100
10
6 bar
4 bar
DN40
DN 100
DN 100
20°C
800 mm
to top of shaft
see data sheet/catalogue
see data sheet/catalogue
see catalogue/see Accessories
H [mm]
A [mm]
1260
-
1560
900
1860
1200
2160
1500
CAUTION! Risk of damage!
The introduction of inadmissible substances
into the drains can cause damage to the product.
Never introduce solids, fibrous substances, tar,
sand, cement, ash, coarse paper, debris, rubbish,
animal waste, grease, oil or swimming pool
water into the drains!
Use of the product as intended also means follow-
ing these instructions.
Use over and beyond the use described is not use
as intended.

5 Product information

5.1
Type code
Example: WS 625 E / 1500
WS
Series: Wilo shaft pump station Synthetic
625
Pump shaft diameter [mm]
E
E = Individual pump
1500
Shaft height [mm]
Note:
in combination with pump MTS 40
in combination with pumps TMW32, TC40
PE pipe, connection via clamp bolting
ground, below depth of 0.5 m
above bottom of shaft, permanent
max. 1 week
Note application according to EN 124!

5.4 Scope of supply

• Wilo DrainLift WS625, consisting of the
components (Fig. 2):
1
plastic shaft
2
internal pipework
2a pressure outlet
2b gate valve
2c pipe screw connection
3
inflow connection with seal
4 connection for ventilation/cable duct with
seal
5
chain hooks

• Installation and operating instructions

NOTE:
If it is to be used as a pump station, accessories are
needed that have to be ordered separately (see
Accessories).
Wilo AG 05/2005