Problems And Solutions - Elvox RS16 Manual Para El Conexionado Y El Uso

Central 24 vcc para cancela corredera acto 404d
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 38
ACTO
10 - Troubleshooting
Problem
The automation system does not work
You cannot save the remote controls
As soon as the gate starts it stops and
reverses
During slowdown, the gate stops
and reverses
Gate movement is reversed
During calibration the motor starts and stops
after 1 second
The gate does not stop after the limit switch
has tripped
During travel calibration, the gate does not
open fully
The gate does not open
22
Cause
No mains supply
Blown fuse
Control and safety inputs not working
Safety devices open
Batteries of the remote control discharged
Remote control not compatible with the first one
saved
When the memory is full, the flashing light will blink
5 times
Motor torque not sufficient
Slowdown speed too low
Wrong opening direction
Encoder not present
Low motor power
The limit switch magnet is too far from the gearmotor
The installer has reversed the 2 magnets
Exceeded the maximum working time
Strong mechanical friction in the gate structure
Exceeded the maximum load capacity in kg of the
gate
Photo-test failed (the flashing light blinks 6 times)
Solution
Check the power line switch
Replace the fuses with others of the same value
Check the diagnosis LEDs (PHC, PHO and STP
must be on)
(PHC, PHO and STP must be on)
Replace the batteries
The first saved remote control configures the
control unit to save only rolling-code remote
controls or only dip-switch remote controls.
Delete at least one remote control or add an
external receiver (the maximum capacity is
50 remote controls)
Increase the power with the POWER trimmer
Set dip-switch 7 ON
Repeat travel calibration, pressing the MEMO RX
button during the first closure
Check the encoder connector is correctly plugged in
Increase the motor power with the POWER
trimmer
Exceeded the maximum load capacity in declared
weight
Move the magnet near to the gearmotor
Check the direction of the magnets
The gate length is more than 6 m
Check the sliding and remove any points of friction
in the gate
Maximum load capacity 400 kg
Check the wiring, see subsection 4.5.3
Photocell engaged
EN
Tabla de contenido
loading

Tabla de contenido