Parameterization - Nominal Current Setting - Phoenix Contact ELR H3-IES-SC-24DC/500AC-0,6 Manual Del Usaurio

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 31
4.2.1. Error acknowledgment
Three different options are available for error acknowledgement:
Manual (Reset button):
• Actuate the Reset button on the device front side.
If the Reset button is actuated again after approx. 2 s, the hybrid motor starter adopts the error status
again.
If the acknowledgment request (pressed reset button) is pending for more than 6 s, the device switches
to the "Parameterization" state.
Manual (remote acknowledgement operating point):
• Connect a button (N/O contact) between the MAN and RES terminals.
An acknowledgement is triggered if a positive edge is identified at the MAN input. If a negative edge is not
identified after approx. 2 s, the hybrid motor starter adopts the error status again, since the possibility of
a manipulation or a defect in the acknowledgement circuit cannot be ruled out.
Automatic:
• Establish an electrical connection between the RES and AUTO terminals.
After the activation of the bimetal monitoring and a subsequent cooling, the device carries out an
automatic acknowledgement.
The RES terminal provides the voltage for a reset.
In variants with the rated control supply voltage of 24 V DC, this is 24 V DC and in the case of
230 V AC, it is a special system voltage.
4.2.2. Feedback
If the hybrid motor starter detects an error, the feedback relay is activated, i.e. the N/O contact is closed
or the N/C contact is opened. This behavior corresponds to that of a motor protecting switch or a
motor overload protection relay.
The feedback is used for signaling and is not a part of the safety chain. It is thus not included in the
safety monitoring.

4.3. Parameterization - Nominal current setting

• Actuate the Reset button for more than 6 s in
order to switch to the "Parameterization"
operating mode; the green LED PWR flashes
again.
In the Parameterization mode, the LEDs are
switched off after every 2 s for 0.3 s in order to
different this mode from other operating modes.
• Set the nominal current of the drive using the
240° potentiometer. The nominal current is
specified in 16 stages. The four LEDs display the
set current.
• Save the value by actuating the Reset button
again (non-volatile range of the data memory).
• Actuate the Reset button for more than 2 s (and
less than 6 s) to display the set current for 3 s.
This function is possible only if
1) the device is not activated, and
2) there is no defect in the device.
From a motor current of 45 A, the
blocking monitoring is activated
(see 8.1. Trigger characteristic).
Code
PWR ERR ladj. ON
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
0
0
1
0
1
0
1
1
0
0
1
1
1
1
0
0
0
1
0
0
1
1
0
1
0
1
0
1
1
1
1
0
0
1
1
0
1
1
1
1
0
1
1
1
1
Nominal current [mA]
Variant:
0.6 A
2 A
9 A
75
180
1500
110
250
2000
145
410
2500
180
560
3000
215
710
3500
250
870
4000
285
1020
4500
320
1170
5000
355
1330
5500
390
1480
6000
425
1630
6500
460
1790
7000
495
1940
7500
530
2090
8000
565
2250
8500
600
2400
9000