28
UK
TIME LEARNING PROCEDURE
To access this procedure, select the menu C21.
CAUTION: Always start with the gate fully closed.
The times are programmed by means of successive start pulses. During the time self-learning phase, C21 blinks
continuously on the display.
During the time self-learning phase, motion always occurs at a non-decelerated speed.
If you want deceleration, remember to activate the option (menu C11) before starting the self-learning procedure:
in this case, the microprocessor will automatically calculate the deceleration time (approximately 20% of the total
time), which will be added at the end of the run time.
The thus defined times can subsequently be modified manually by accessing the dedicated menus and changing
the numerical data.
1-motor configuration
the gate starts opening.
• START
• When the gate arrives at the desired opening position
• Counting of the pause time during opening starts.
• When the desired pause time has elapsed
• When the gate arrives at the closing position
2-motor configuration
the gate 1 starts opening.
• START
• Gate 2 automatically starts after 3 seconds.
• When the gate 1 arrives at the desired opening position
• When the gate 2 arrives at the desired opening position
• Counting of the pause time during opening starts.
• When the desired pause time has elapsed
• Gate 1 automatically starts after 5 seconds.
• When the gate 2 arrives at the closing position
• When the gate 1 arrives at the closing position
NB: In case of deceleration, the deceleration time must be subtracted from the run time
Example: Run time shown on the display H1=15 H2=20 H3=3 becomes H1= 12 H2=17 H3=3
• To exit the procedure once the above described steps have been carried out, press the ESC button until the horizontal lines
appear on the display.until the horizontal lines appear on the display.
USING THE LIMIT SWITCHES
If the deceleration function is enabled, the limit switches mark the start of the deceleration period. The gate continues the
decelerated motion for the time set in the menus H3 and H6.
Make sure that you set the run times longer than the time necessary to reach the limit switch.
If deceleration is not enabled, the limit switches stop the motion.
START
the gate stops.
START
the gate starts closing.
START
the gate stops.
START
the gate 1 stops.
START
the gate 2 stops.
START
the gate 2 starts closing.
START
the gate 2 stops.
START
the gate 1 stops.
BA230