Electrical Connections; Signalling Led - RIB R-CRX 2.0 Manual Del Usuario

Cuadro de mando programable para persianas
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

3. Electrical connections

The control unit is supplied with all the inputs normally closed and jumpered to the common.
Before connecting a device to the control unit remove the jumper corresponding to the device that you want to connect leaving the others unchanged.
17
GND
18
ANT
11
N
230Vac o/ou/or 120Vac
10
L
16
L
LIGHT
15
N
14
V
L
13
W
L
12
U
N
COM
2
1
STOP
OPEN
3
2
COM
CLOSE
4
2
COM
PHOTO
5
2
COM
7
-
24Vdc
6
+

4. Signalling led

"Power On": lighted when the control unit is powered.
"Photo": lighted if the photocell contact is closed.
Connect the aerial cable.
Central wire to terminal 18
Shield to terminal 17
Connect the power supply cable between the clamps 10 and 11
of the control unit.
Connect an eventual courtesy light between the clamps 15 and
16 of the control unit.
• Connect the neutral of the motor to the clamp 12 "U" of the
control unit.
• Connect the phase "1" of the motor to the clamp 13 "W" of
the control unit.
• Connect the phase "2" of the motor to the clamp 14 "V" of the
control unit.
Connect the NORMALLY CLOSED contact of the STOP to the
clamp 1 and 2 of the terminal board.
WARNING : jumper the input 1 to the input 2 if not used.
Connect the OPEN button between the clamp 2 and 3 of the
terminal board.
Leave it opened if not used.
Connect the CLOSE button between the clamp 2 and 4 of the
terminal board.
Leave it opened if not used.
Connect the NORMALLY CLOSED contact of the photocell
(PHOTO) between the clamp 2 and 5 of the control unit.
WARNING: jumper the input 2 to the input 5 if not used.
Connect the power supply of the accessories to the clamp 6 and
7 of the terminal board.
A piece of wire is already present in terminal 18, and this can
guarantee an acceptable range for the radio signal.
Power supply 230 Vac 50 Hz (Optional 120 Vac 60 Hz)
Do not connect the card directly to the electric network.
Put a device which can ensure the disconnection of each pole from
the power supply of the control unit.
Connecting a charge of 230Vac (or 120Vac) 500W MAX it is possible
to light up the operating zone of the automation during each motion.
The turning off is timed with a period of 3 minutes.
The counting is reset at each impulse of up or down.
Check that the motor wiring is compliant with the installation.
To do this, follow the procedure of the preliminary checks.
If the STOP input is open, then this causes the immediate stop of
the automation
The activation of the OPEN button gives an opening impulse to the
automation.
The activation of the CLOSE button gives a closing impulse to the
automation.
The PHOTOCELL (PHOTO) can cause the STOP of the automation
or the motion inversion .
See chap.9
WARNINGS: the control unit gives a voltage of 24 Vdc.
"Stop": lighted if the contact stop is closed.
17
G
B