• 01 – After 1 Hour
• 02 – After 2 Hours
• 03 – After 4 Hours
• 04 – After 8 Hours
• 05 – After 12 Hours
• 06 – After 24 Hours
3. Press [*] to accept the selection.
4. Press [#] to exit the section.
NOTE: For UL Residential Burglary (UL1023), Home Health Care (UL1637), ULC
Residential Burglary (ULC/ORD-C1023) installations, the maximum Supervision window
shall be set to 24 hours.
For UL Residential Fire (UL985) installations, the maximum supervision window is set to 200s.
For UL Commercial Burglary (UL1610/UL365) and ULC Residential Fire (ULC-S545), the maximum
supervision window shall be set to 4 hours.
[804][810] Wireless Options
To program wireless options:
1. Enter Installer Programming section [804][810].
2. Select one of the following options by scrolling or entering the hotkey:
01 – RF Delinquency
02 – Wireless Supervisory/ RF Jam Alarm
03 – Wireless Tamper
04 – 200s Fire Supervision
3. Press [*] to accept the selection and [#] to exit.

[804][841] Motion Cameras

To program wireless options:
1. Enter Installer Programming section [804][841].
Select one of the following options by scrolling or entering the hotkey:
001
Visual Verification
002
View Time Window
003
View Other Alarms
On: Alarms trigger image capture from PIR
Cameras
Off: Alarms do not trigger image capture from
PIR Cameras
01 Alarm + 5 Minutes
02 Alarm + 15 minutes
03 Alarm + 1 Hour
01 Fire enabled/disabled
02 Duress enabled/disabled
03 Medical enabled/disabled
04 Panic enabled/disabled