63A energy meter,
direct connection
5. CONNECTIONS
Wiring diagrams:
L1
N
1
11
3
L1
L2
L3
*
N
* 3N-3E
Terminal board marking and diagram combination:
T1 / T2
RS485
E
SG
1
C
+
–
12 / 24V d.c.
OUTPUT
INPUT
E
1
C
12 / 24V d.c.
Max. 30V 50mA
MBUS
T1 / T2
E
1
C
A
B
12 / 24V d.c.
Technical data sheet: IDP000189EN_01
L2
L3
4
6
7
9
T1/T2 (INPUT)
1 C
Modbus RS485
+
MBUS
A B
Codes: CE4DF30PCL1 – CE4DF3DTCL1 – CE4DF3MTCL1
Model: CONTO D4-Pd
6. OPERATING DATA
6.1 ELECTRIC DATA
Currents:
- Reference current, I
- Minimum current, I
- Maximum current, I
Rated voltages:
- Three-phase rated voltage Un: 3x230V∼ / 3x400V∼ ±15%
Rated frequency:
- F
: 50Hz; 60Hz
n
- Permitted variation: 49...51Hz; 59...61Hz
Connectable section:
- Copper wires
- Voltage connection terminals (L1, L2, L3, N):
Rigid wire
Flexible wire
- Terminal boards in the upper part of the meter (input, impulse
output and Mbus):
Rigid wire
Flexible wire
:
Necessary tools
- For the voltage connection terminals (L1, L2, L3): screwdriver
with 6mm blade or Pozidriv No. 2
- For the Neutral (N) connection terminal: screwdriver with 6mm
blade or Pozidriv No. 2
- For the terminal boards in the upper part of the meter (input,
SG
impulse output and bus): screws with 2.5mm blade
Updated: -
: 5A
ref
: 0,25A
min
: 63A
max
Without bush
With bush
1 x 0,75 ÷ 16 mm²
1 x 0,75 ÷ 10 mm²
1 x 4 ÷ 10 mm²
Without bush
With bush
1 x 0,2 ÷ 1,5 mm²
1 x 0,2 ÷ 1 mm²
1 x 0,2 ÷ 1 mm²