G
B
RESERVED > CONNECTOR RESERVED TO FACTORY CONTROLS.
RUN > TRIMMER FOR MOTOR SPEED ADJUSTMENT.
With this trimmer it is possible to adjust the motor speed (set by default at half the speed).
The adjustment is quite useful to align the automation with the European standards on
impacts.
For gates weighing from 0 to 200 kg is recommended to set the RUN trimmer from
1/2 to MAX.
For gates weighing from 200 to 400 kg is recommended to set the RUN trimmer from
MIN to 1/2.
Note: the slow motion is not adjustable, as it is calculated automatically.
TCA > FULL OR PEDESTRIAN AUTOMATIC CLOSING TRIMMER
Not enabled by default and led DL3 off (trimmer rotated fully counter-clockwise).
With this trimmer it is possible to adjust the time before the full or pedestrian automatic
closing.
Full or pedestrian automatic closing can be enabled only with the door fully (full) or partly
(pedestrian) open and led DL3 on (with trimmer rotated clockwise).
The pause time can be adjusted from a minimum of 2 seconds to a maximum of 2 minutes.
GRADUAL START
If DIP 3 is ON, gradual motion for 1 second is enabled with every start.
LED SIGNALS
DL1
programming signal enabled
DL2
encoder status signal
DL3
automatic closing time signal
DL4
manual unlock micro-switch signal
DL5
closing gate signal
DL6
opening gate signal
DL7
closing limit switch signal
DL8
opening limit switch signal
DL9
3.3V micro-controller voltage presence signal
DL10
radio code programming signal
DL11
programmer connected signal
DL12
stop contact signal
DL13
photocell contact signal
DL14
edge contact signal
Buzzer
> signals various functions, see table of visual and sound signals.
Fuses
F2
T 300 mA functional logic safety fuse
F3
T 10 A
motor safety fuse
C – ADJUST STROKE IN LINE WITH ELECTRICAL OR MAGNETIC LIMIT
SWITCHES
This control has the task of facilitating system commissioning or any subsequent adjustments
for the installer.
N.B. : During this control the safety functions SF1 (Safety edge), SF2 (Photocells), SF3 (Stop
button) and SF4 (Impact sensor) are NOT active.
1 - Unlock the operator using the manual release and position the limit switch cams on the
rack, so as to define the gate stroke.
2 - Bring the gate to mid-stroke position and lock the operator.
3 - Set DIP 1 to ON mode = > led DL1 starts flashing.
4 - Press and hold the PROG button (the command is operator-run, open-stop-close-stop-
open-etc...) = > the gate starts at high speed and then slows down until it reaches the
limit stop. Check that the gate stops in the desired position. If not, move the limit switch
cams and try again. Check the limit switch on the opposite side.
5 - You can adjust the high speed during the first 5 seconds of operation by rotating the RUN
trimmer. Rotating the RUN trimmer clockwise, the speed increases. The RUN trimmer is
set by default to mid-stroke.
6 - When done, reset DIP 1 to OFF. Led DL1 goes off signalling exit from the control.
IMPORTANT: During this operation, the stop button, edges and photocells are not
enabled.
D – PROGRAMME FULL OPENING
NB. : During the programming phase, the safety functions SF1 (Safety edge), SF2
(Photocells), SF3 (Stop button) and SF4 (Impact sensor) are active and their
performance level is PL "b" according to EN13849-1. Their intervention stops
the programming (led DL1 shifts from flashing to on steady).
Caution: If the inputs STOP, PHOT and EDGE are not connected, run jumpers between
COM-STOP, COM-PHOT and COM-EDGE before you proceed with programming.
N.B. : In this case, the safety functions SF1 (Safety edge), SF2 (Photocells),
SF3 (Stop button) are NOT active.
1 - IMPORTANT: TO PROPERLY PROGRAMME THE OPENING, YOU MUST POSITION THE
GATE AT ABOUT 20 CM FROM THE CLOSING LIMIT-SWITCH.
2 - Set DIP 2 to ON mode = > led DL1 starts flashing.
3 - Press the PROG button or the remote control button (if previously memorized) dedicated
to the total opening. The gate will begin a series of movements. DO NOT PASS IN FRONT
OF THE PHOTOCELLS WHILE THE GATE IS MOVING.
4 - The programming stops when the gate is closed and led DL1 is off.
5 - Set DIP 2 to OFF.
Note well: If at the end of the programming procedure the trimmer RUN is moved, the
Note: the low speed starting point is calculated automatically by the control unit during the
time programmin procedure. It will start 50 ÷ 60 cm before reaching the opening or
closing limit stop.
To repeat the programming procedure, position the DIP 2 in the OFF mode, and
by using the procedure "C – Adjust stroke in line with electrical or magnetic limit
switches" close the gate almost completely, leaving it open for 20 cm. Then, repeat
the programming procedure as described above.
E – PROGRAMME PEDESTRIAN OPENING
NB. : During the programming phase, the safety functions SF1 (Safety edge), SF2
(red)
(Photocells), SF3 (Stop button) and SF4 (Impact sensor) are active and their
(green)
performance level is PL "b" according to EN13849-1. Their intervention stops
(red)
the programming (led DL1 shifts from flashing to on steady).
(red)
When the gate is closed:
(red)
1 - First, set DIP 2 to ON and then DIP 1 to ON. Led DL1 starts flashing.
(green)
2 - Press the pedestrian button (COM-PED) or the remote control button (if previously
(red)
memorized) dedicated to the pedestrian opening = > The gate opens.
(green)
3 - Press the pedestrian button to stop the gate (the pedestrian opening stroke of the gate is
(yellow)
now set). After 2 seconds the gate will automatically close..
(two colours)
4 - When done programming the pedestrian opening, set DIP 1 and 2 to OFF.
(red)
To repeat the programming procedure, position DIP 1 and DIP 2 to OFF and by using
(red)
the procedure "C – Adjust stroke in line with electrical or magnetic limit switches"
(red)
close the gate completely. Then, repeat the programming procedure as described
(red)
above.
F - FULL OPENING RADIO CODES PROGRAMMING (MAX 1000 CODES)
CAUTION: before you save the remote controls, use DIP 14 to choose which remote
DIP 14 set to OFF: you can save remote controls with variable code SUN-PRO:
SUN-PRO 2CH dual channel - red keys and white led code ACG6210
SUN-PRO 4CH quadruple channel - red keys and white led code ACG6214
SUN-PROX 2CH dual channel - red keys and yellow led code ACG6220
SUN-PROX 4CH quadruple channel - red keys and yellow led code ACG6224
DIP 14 set to ON (default): you can save remote controls with fixed code SUN and MOON:
SUN 2CH dual channel - blue keys and white led code ACG6052
SUN 4CH quadruple channel - blue keys and white led code ACG6054
SUN CLONE 2CH dual channel - blue keys and yellow led code ACG6056
SUN CLONE 4CH quadruple channel - blue keys and yellow led code ACG6058
MOON 2CH dual channel - black keys and yellow led code ACG6081
MOON 4CH quadruple channel - black keys and yellow led code ACG6082
CAUTION: You cannot save remote controls with fixed code and remote controls with
The remote controls can be programmed only when the gate is at a standstill.
1 - First, set DIP 1 to ON and then DIP 2 to ON. Programming led DL10 flashes red for 10
seconds.
2- Within these 10 seconds, press the remote control button (normally channel A). If the
remote control has been saved correctly, two-tone led DL1 turns green and a buzzer
tone confirms the saved entry. The 10 seconds for programming the codes are reset
automatically with two-tone led DL10 that flashes red to save the next remote control.
3 - To finish programming, let the 10 sec pass or press briefly the PROG. button.
Programming led DL10 stops flashing.
4 - Reset DIP 1 to OFF and DIP 2 to OFF.
5 - End of sequence.
DELETING ALL RADIO CODES RESERVED TO FULL OPENING
The codes can be deleted only when the gate is at a standstill.
32
programming procedure must be repeated.
controls to use:
variable code simultaneously.