4. Remove insulation
Refer to Table 3 and cutback the insulation as shown.
Table 3
Maximum
Connector Dimensions
Kit
Length "Y"
HVS-2521S
4.0" (102mm)
HVS-2522S
6.0" (152mm)
HVS-2523S
8.0" (203mm)
5. Abrade insulation
Abrade the insulation, as necessary to remove imbedded semi-con,
and clean.
6. Clean cable jacket
Clean cable jacket(s) for the length of the nested tubes as shown.
7. Place nested tubes over cable
Protect tubes from end of conductor as they are placed over cable
end.
8. Install connector
After installation, deburr connector.
Using an oil-free solvent, clean the insulation as shown.
9. Apply SRM over connector
Remove backing from one side of the long strip of Stress Relief
Material (SRM). Roll the SRM and remaining backing strip into a
convenient size. Remove the remaining backing strip and tightly
wrap the SRM around the connector and exposed conductor. Be
sure to fill the gaps and low spots around the connector.
Continue to wrap SRM onto the solvent cleaned insulation as shown
Note: Do not over apply. The finished SRM diameter should be only
slightly larger than that of the cable insulation. Discard any excess
SRM (long strips).
PII 53105
Revision AK
Expansion
Diameter "Z"
Gap "X"
1.00" (25mm)
1/4" (5mm)
1.55" (39mm)
1/2" (10mm)
1.85" (47mm)
1/2" (10mm)
Z
Insulation
X
Cutback
Y
Abrade
Insulation
30"
Clean
(760mm)
Semi-Con
Metallic Shield
1/4"
(5mm)
3
"Z"
"X"
=
+
1/2 Length
Expansion
Gap
of Connector
Abrade
Insulation
Clean
Insulation
Insulation
Connector
Semi-con
Stretch SRM to
1/2 Original Width
Fill gaps
1/4"
(5mm)
SRM
PCN 625799-000
Effective Date: June 17, 2010
"Y"
400
249
271
107
385
387
273