WARNING
To reduce the risk of fire or explosion, DO
NOT CONNECT THE GAS LINE TO THE
TUMBLER IF THE GAS SERVICE IS NOT
THE SAME AS THAT SPECIFIED ON THE
TUMBLER SERIAL PLATE! It will first be
necessary to convert the gas burner
orifice and gas valve. Appropriate
conversion kits are available.
IMPORTANT: Any product revisions or conversions
must be made by the Manufacturer's Authorized
Dealers, Distributors or local service personnel.
IMPORTANT: The tumbler must be isolated from
the gas supply piping system by closing its
individual manual shut-off valve during any
pressure testing of the gas supply piping system at
test pressure equal to or less than 1/2 psig
(3.45 kPa, 34.5 mbar).
IMPORTANT: The tumbler and its manually
operated appliance gas valve must be disconnected
from the gas supply piping system during any
pressure testing of that system at test pressures in
excess of 1/2 psi (3.45 kPa, 34.5 mbar).
IMPORTANT: The installation must comply with
local codes or, in the absence of local codes:
with the latest edition of the "National Fuel
G
Gas Code," ANSI Z223.1/NFPA 54 in the
U.S.A.,
with CSA-B149.1 or Natural Gas and Propane
G
Installation Code in Canada,
and Australian Gas Association/Australian
G
L.P. Gas Association requirements in
Australia.
70268201

Gas Requirements

W060
© Published by permission of the copyright owner – DO NOT COPY or TRANSMIT
Obtain specific gas service pipe size from the gas
supplier. Refer to Table 9 for general pipe size.
A dirt and water vapor pipe trap must be furnished and
installed. Refer to Figure
Install a 1 inch (25.4 mm) pipe gas loop to maintain
equal pressure at all gas connections. Refer to
Figure 14.
An in-line pressure regulator may be required on
Natural Gas models if the line pressure exceeds
8 water column inches (2.00 kPa) pressure with all gas
appliances firing.
WARNING
To reduce the risk of fire or explosion, if
the tumbler is to be connected to
Liquefied Petroleum (L.P.) gas, a vent to
the outdoors must be provided in the
room where the tumbler is installed.
NATURAL GAS service must be supplied at 7.0 ±
1.5 inch water column pressure (1.74 ± 0.37 kPa).
L.P. (Liquefied Petroleum) GAS service must be
supplied at 11 ± 0.3 inch water column pressure
(2.74 ± 0.07 kPa).
EUROPEAN GASES – The above data for Natural
and L.P. Gas does not apply in the EU. Refer to
Installing Gas Drying Tumblers in the European
Union.
Pressure checks can be made at the shut-off valve.
Refer to Figure 13.