8. Technical specifications
ECOmulti
PowerControl / PowerAssist
AC input
Maximum feed through current
Minimum AC power flow capacitiy for
PowerAssist (A)
INVERTER
Input voltage range (V DC)
Output
(1)
Cont. output power at 25°C / 77°F (VA)
Cont. output power at 25°C / 77°F (W)
Cont. output power at 40°C / 104°F (W)
Cont. output power at 65°C / 150°F (W)
Peak power (W)
Maximum efficiency (%)
Zero-load power (W)
Zero-load power in AES mode (W)
Zero-load power in Search mode (W)
CHARGER
AC Input
Charge voltage 'absorption' (V DC)
Charge voltage 'float' (V DC)
Storage mode (V DC)
Charge current house battery (A)
Charge current starter battery (A)
Battery temperature sensor
GENERAL
Auxiliary output
Programmable relay
(5)
Protection
(2)
Common Characteristics
ENCLOSURE
Common Characteristics
Battery-connection
230 V AC-connections
Weight (kg)
Dimensions (hxwxd in mm)
STANDARDS
Safety
Emission / Immunity
Uninterruptible power supply
Anti-islanding
1) Can be adjusted to 60 Hz; 120V 60 Hz on request
2) Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 230 VAC on inverter output
g. Input voltage ripple too high
3) Non linear load, crest factor 3:1
4) At 25°C ambient
5) Programmable relay which can be set for general
alarm, DC undervoltage or genset start/stop function
AC rating: 230V / 4A
DC rating: 4A up to 35VDC and 1A upto 60VDC
Input voltage range: 187-265 VAC
Output voltage: 230 VAC ± 2%
(3)
Input voltage range: 187-265 VAC
(4)
Max. 32A Switches off when no external AC source available
Operating temp.: -40 to +65°C (-40 – 150°F) (fan assisted cooling)
Material & Colour: aluminium (blue RAL 5012) Protection category: IP 20, pollution degree 2, OVC3
EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3
VDE-AR-N 4105, G83/2, AS/NZS 4777.2, NRS 097-2-1, RD 1699/2011 y RD 413/2014, C10/11,
24/3000/70-50 230V
Yes
Input frequency: 45 – 65 Hz
50A
5,3
19 – 33
Frequency
3000
2400
2200
1700
6000
94
20
15
10
Input frequency: 45 – 55 Hz
28,8
27,6
26,4
70
4
Yes
Yes
a - g
Humidity (non-condensing): max 95%
M8 bolts (2 plus and 2 minus connections)
Screw terminals 13 mm² (6 AWG)
30
478 x 579 x 337
EN 60335-1, EN 60335-2-29, IEC62109-1, IEC62109-2
IEC 61000-6-1, EN 61000-6-2, EN 61000-6-3
IEC 62040-1, AS 62040.1.1
UTE C15-712-1
50 Hz ± 0,1%
:
Power factor: 1
17