ABLE OF OVERLOAD TIMES
OVERLOAD TIMES
100% < Load  125%
125% < Load  150%
Load > 150%
OPERATION FROM
BYPASS
Activates bypass after 2 sec
Shutdown after 120 sec
Activates bypass after 2 sec
Shutdown after 4 sec
Activates bypass instantaneously
Shutdown after 1 sec
T
ECHNICAL DATA TABLE
INVERTER
Shutdown after 60 sec
Shutdown after 4 sec
Shutdown after 0.5 sec