Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

ALARM CODES

Using a sophisticated self check system, the UPS can verify and indicate on the display panel any faults
and/or malfunctions that may occur during the normal operation of the device. In the event of a problem, the
UPS indicates this by displaying the code and the type of alarm (FAULT and/or LOCK).
FAULT
FAULT signals can be subdivided into three categories.
1. Faults: these are "minor" problems that do not stop the UPS but reduce performance or prevent the
use of some of its functions.
CODE
A06
A08
A11
A54
A61
A62
A63
2. Alarms: these are more critical problems than faults since if they persist, even for a very short time,
they may cause the UPS to stop.
CODE
F03
F04
F05
F07
F10
F13
F21
F40
F41
F42
F43
F50
F51
F52
F53
F55
F60
DESCRIPTION
Sensor1 temperature less than 0°C
Sensor2 temperature less than 0°C
Input relay locked (does not open)
Load > preset user threshold
Batteries to be replaced
No Battery box or not connected
Waiting to recharge batteries
DESCRIPTION
Auxiliary power supply not correct
Dissipators overtemperature
Temperature sensor1 faulty
Temperature sensor2 faulty
Input fuse broken or input relay locked (does not close)
Condenser precharge failed
Condenser bank overvoltage
Inverter overvoltage
Direct voltage in output
Inverter voltage not correct
Inverter undervoltage
Overload: load > 103%
Overload: load > 125%
Overload: load > 150%
Short circuit
Waiting for reduction of load to return onto inverter
Batteries overvoltage
TROUBLESHOOTING
61

Hide quick links:

Tabla de contenido

Solución de problemas

loading

Tabla de contenido