Hergom H-03 Serie Instrucciones Para La Instalación, Uso Y Mantenimiento página 25

Hogar de empotrar gama completa
Ocultar thumbs Ver también para H-03 Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

It is essential that the casing which is used to surround you H03 TURBOCONVECTOR wood
burner has a removable panel so as to be able to access the ventilator and its connections in
the future if necessary.
The chamber where the H03 TURBOCONVECTOR wood burner is installed must have an air
inlet in its lower section which is sufficient for supplying the ventilator. Is it advisable that the air
inlet of the ventilator is carried out if possible from outside the house or failing that from
another room separate to the one where the wood burner is installed. The grate will have a
minimum free flow section of 400 cm
depressions within the chamber which could suck in smoke from the wood burner.
It is necessary to place a grate on the upper section of the casing to dissipate the heat from
this chamber so as to prevent cracks being produced in the casing due to accumulated excess
heat.
The optimum form of air distribution is to place commercial adjustable grates on the outlets to
the various rooms, in such a way that you can choose at any time to which places you want to
direct the flow of hot air.
B-Operation of forced convection
The fan connected to the network, that will work according to the following guidelines:
Manual mode
The control module operates the fan in four possible operating speeds, driven by the remote
control buttons which are configured as follows:
-A Button: speed increases
-Button B: speed decreases
-Button C: directly activates Pot. max
-D-Button: stops and auto mode
Left: remote control with 4 buttons. Right: NTC temperature probe.
The fan will turn off automatically if past 3 o'clock, the temperature sensed by the NTC does not
exceed a minimum value.
Automatic mode
When the array is connected to the 220 V. AC or pressing the button-the-D remote
control mode remains the surveillance module with the fan stopped.
When the temperature sensed by the probe NTC temperature exceeds minimum
recorded as running in the control module the fan rotates at high speed while remaining
on this speed while the temperature is higher than the minimum recorded as stop.
STARTING
STOP
Also put on the fan, at any temperature, when the
NTC probe is disconnected or faulty, as the security mode.
2
, which will not be able to be closed, to prevent
Temperature probe NTC
Rises above 40 ° C
Drops below 45 ° C
25
Tabla de contenido
loading

Este manual también es adecuado para:

H03-70H03-80

Tabla de contenido