Performance PRo standard settings
PRoGRaM THe THeRMosTaT
PRoGRaM THe THeRMosTaT
PRoGRaM THe THeRMosTaT
The T4900 School Series may also be operated with standard Performance PRO settings.
Each day has two or four scheduled events per day (Occupied1,Occupied2, unocc1, and
unocc2), depending on user selection. Each one of these events can be programmed with a
start time and Heat and Cool Setpoints. Heat Setpoint controls the heating system during cold
weather. Cool Setpoint controls the cooling system during hot weather. T4900 School Series is
preprogrammed with factory default settings for seven days of the week as follows:
Time Period
Occupied1
unocc1
Occupied2
unocc2
i
note: To change the preprogrammed times and/or setpoint temperatures, follow the
instructions under "Program scheduled events."
i
note
See Service Menu 240 to enable four scheduled events per day.
:
start Time
6:00 am
8:00 am
6:00 pm
10:00 pm
Heat setpoint
Temperature
68° F (20° C)
62° F (16.5° C)
64° F (18° C)
58° F (14.5° C)
Cool setpoint
Temperature
76° F (24.5° C)
83° F (28.5° C)
81° F (27° C)
85° F (29.5° C)
19